The development characteristics of the discontinuous leader under the positive switching impulse with low rate of voltage rising

被引:6
作者
Xie, Yaoheng [1 ]
Yishi, Yue [1 ]
Ye, Huisheng [1 ]
Yun, Liu [1 ]
Zhong, Yongheng [1 ]
Zhao, Xiangeng [2 ]
机构
[1] State Grid Hunan Elect Power Co, Elect Power Res Inst, Changsha 410007, Hunan, Peoples R China
[2] China Southern Power Grid, Elect Power Res Inst, Guangzhou 510080, Guangdong, Peoples R China
关键词
LONG AIR-GAPS; CORONA DISCHARGE; MODEL; PROPAGATION; BREAKDOWN;
D O I
10.1051/epjap/2018180103
中图分类号
O59 [应用物理学];
学科分类号
摘要
Discontinuous leader development is the most important discharge process under the application of the switching impulse voltage with the low rate of voltage rising, which is of great significance to study the external insulation characteristics of ultra-high voltage (UHV) large scale air gap. Based on the CMOS high-speed camera, a discharge test with different operating impulse voltage is carried out by constructing a comprehensive observation platform of rod-plate air gap discharge, and a clear discontinuous leader development process picture is captured. Moreover, the leader current, injection charge and leader channel unit length charge, and their characteristics of the change trend are also obtained. Further analysis based on the experimental results shows that the discontinuous leader development under the action of the impulse voltage with low rate of voltage rising has two different laws. Finally, this paper uses the thermodynamic equation, combined with the test results, the channel temperature changes in the discontinuous leader development stagnation stage were calculated. The results show that the leader channel temperature is still greater than 1500 K in the hundreds of microsecond time scales in the leader stagnation stage, and the subsequent leader can continue to develop on the original leader channel.
引用
收藏
页数:7
相关论文
共 20 条
  • [1] SWITCHING SURGE STRENGTH OF LARGE AIR GAPS - PHYSICAL APPROACH
    CARRARA, G
    THIONE, L
    [J]. IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1976, 95 (02): : 512 - 524
  • [2] D'Alessandro F., 2001, IEEE T DIELECT EL IN, V11, P638
  • [3] PROPAGATION OF THE POSITIVE STREAMER-LEADER SYSTEM IN A 16.7 M ROD-PLANE GAP
    DOMENS, P
    GIBERT, A
    DUPUY, J
    HUTZLER, B
    [J]. JOURNAL OF PHYSICS D-APPLIED PHYSICS, 1991, 24 (10) : 1748 - 1757
  • [4] Experimental study and analysis of corona discharge parameters on an ice surface
    Farzaneh, M
    Fofana, I
    [J]. JOURNAL OF PHYSICS D-APPLIED PHYSICS, 2004, 37 (05) : 721 - 729
  • [5] Fundamental processes in long air gap discharges
    Gallimberti, I
    Bacchiega, G
    Bondiou-Clergerie, A
    Lalande, P
    [J]. COMPTES RENDUS PHYSIQUE, 2002, 3 (10) : 1335 - 1359
  • [6] Gallimberti I., 1979, Journal de Physique Colloque, V40, pC7/193, DOI 10.1051/jphyscol:19797440
  • [7] Implementation of a discharge propagation model using an electric field map: an attempt toward a design tool for high-voltage overhead insulation
    Giralt, M
    Buret, F
    [J]. JOURNAL OF PHYSICS D-APPLIED PHYSICS, 2000, 33 (05) : 504 - 516
  • [8] A simplified model for the simulation of positive-spark development in long air gaps
    Goelian, N
    Lalande, P
    BondiouClergerie, A
    Bacchiega, GL
    Gazzani, A
    Gallimberti, I
    [J]. JOURNAL OF PHYSICS D-APPLIED PHYSICS, 1997, 30 (17) : 2441 - 2452
  • [9] Numerical modelling of inhibited electrical discharges in air
    Larsson, A
    Bondiou-Clergerie, A
    Gallimberti, I
    [J]. JOURNAL OF PHYSICS D-APPLIED PHYSICS, 1998, 31 (15) : 1831 - 1840
  • [10] Les Renardieres Group, 1986, IEE P, V7, P410