Study on Electrical Parameter Frequency of the Out-of-step Oscillation Center

被引:1
作者
Yang Jian [1 ]
Tang Fei [1 ]
Liao Qingfen [1 ]
Wang Yifei [1 ]
机构
[1] Wuhan Univ, Sch Elect Engn, Wuhan 430072, Hubei Province, Peoples R China
来源
Applied Decisions in Area of Mechanical Engineering and Industrial Manufacturing | 2014年 / 577卷
关键词
out-of-step; current frequency; voltage frequency; oscillation center;
D O I
10.4028/www.scientific.net/AMM.577.536
中图分类号
TH [机械、仪表工业];
学科分类号
0802 ;
摘要
Out-of-step splitting is an emergency strategy to trigger splitting devices to separate power systems into several sub-regions through capturing oscillation center before the collapse of the system. How to position the oscillation center rapidly and accurately is a key procedure in out-of-step splitting field. This paper proposes a new method to position the oscillation center based on electrical parameter frequency. Firstly the current and voltage frequency variation characteristic of out-of-step tie line is analyzed. Secondly, the electrical parameter frequency variation rules are summarizes, i.e. curves of buses voltage frequency of the oscillation center line change continuously without intersection and they have the opposite variation trend. At last, the oscillation center can be positioned accurately within half out-of-step cycle by constantly monitoring electrical parameter frequency of the transmission tie lines. The accuracy and rapidity of the method are certified by the simulation results of four machine two regional power system.
引用
收藏
页码:536 / 540
页数:5
相关论文
共 5 条
  • [1] Gao Peng, 2005, Automation of Electric Power Systems, V29, P38
  • [2] Gao Peng, 2005, Automation of Electric Power Systems, V29, P15
  • [3] Gao Peng, 2005, AUTOMATION ELECT POW, V28, P36
  • [4] Li Li, 2009, Automation of Electric Power Systems, V33, P40
  • [5] Zhang Bao-hui, 2001, Proceedings of the CSEE, V21, P67