共 11 条
Analytical Study on Electron Avalanche in Two Different Temperature and Pressure Regions for High-temperature SF6 Gas
被引:2
作者:
Kuroda, Mami
[1
]
Yokomizu, Yasunobu
[2
]
Terada, Masanao
[1
]
Kotsuji, Hideyuki
[1
]
Shiraishi, Katsuhiko
[1
]
Urai, Hajime
[3
]
机构:
[1] Hitachi Ltd, R&D Grp, Ctr Innovat Energy, Hitachi, Ibaraki, Japan
[2] Nagoya Univ, Grad Sch Engn, Dept Elect Engn, Nagoya, Aichi, Japan
[3] Daido Univ, Dept Elect & Elect Engn, Nagoya, Aichi, Japan
来源:
2022 6TH INTERNATIONAL CONFERENCE ON ELECTRIC POWER EQUIPMENT - SWITCHING TECHNOLOGY (ICEPE-ST)
|
2022年
关键词:
High-voltage circuit breaker;
hot SF6 gas;
electron avalanche;
HOT SF6;
BREAKDOWN;
D O I:
10.1109/ICEPE-ST51904.2022.9757123
中图分类号:
TM [电工技术];
TN [电子技术、通信技术];
学科分类号:
0808 ;
0809 ;
摘要:
High-voltage circuit breakers require a thorough understanding of the dielectric phenomena in the arcing region under non-uniform temperature and pressure conditions. As the first step towards reaching this understanding, we analyzed the development of electron avalanche using one-dimensional flow simulation considering 26 collisional reactions between electrons, ions, and neutral particles in a high-temperature/low-pressure region and a low-temperature/high-pressure region. The higher critical electric field in the latter region resulted in a lower possibility of electron avalanche development. The effect of electron avalanche in a gas area with largely different critical electric fields can be calculated by using the proposed analysis model for electron avalanche development.