Improvement of the Standard Ampacity Calculations for Power Cables Installed in Trefoil Formations in Ventilated Tunnels

被引:6
作者
Colef, John-Michael [1 ]
de Leon, Francisco [1 ]
机构
[1] New York Univ, Metrotech Ctr 5, Dept Elect & Comp Engn, Brooklyn, NY 11201 USA
关键词
Mathematical model; Power cables; Standards; Convection; IEC Standards; Ventilation; Finite element analysis; Cable rating; computational fluid dynamics (CFD); forced convection; turbulent flow; ventilated tunnel;
D O I
10.1109/TPWRD.2021.3068111
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Forced ventilated underground installations are challenging to design due to the complex mathematics of turbulent fluid flow. Previous methods have tackled this problem, but only recently, the effect of confinement on a single cable has been considered. In this paper, the effect of cable confinement on the practical case of ventilated trefoil installations is investigated. The complete Computational Fluid Dynamics (CFD) problem is solved using Finite Element Method (FEM) simulations and then validated by laboratory experiments using pipes. FEM simulations are then used to vary the current, the wind velocity, and the distance of the trefoil from the tunnel wall to get a comprehensive picture of the phenomena. This data is used to create a new empirical equation for the Nusselt number for a wide range of operating conditions. The principle of similitude is validated for a scaled-down model of a large tunnel and then used to analyze the thermal rating of tunnels. The new equation improves the IEC standard equations by accounting for the effect of cable confinement on trefoil installations. An important finding of this paper is that a lower maximum permissible current rating is obtained, which if ignored can present a serious risk for thermal damage. It was also found that the cables must be installed three cable diameters away from the wall to prevent the derating effect of confinement.
引用
收藏
页码:627 / 637
页数:11
相关论文
共 34 条
[1]  
Anders G. J, 1997, RATING ELECT POWERCA, V1st
[2]  
[Anonymous], 2013, 60 500 KV HIGH VOLT
[3]  
[Anonymous], 2017, IEC6028723
[4]  
[Anonymous], 2014, CIGR SESS 45 45 INT
[5]  
[Anonymous], 1995, 60287 IEC, P1994
[6]  
Boukrouche F., 2016, P 7 EUR THERM SCI C
[7]   Mock-Up Study of the Effect of Wall Distance on the Thermal Rating of Power Cables in Ventilated Tunnels [J].
Boukrouche, Fahd ;
Moreau, Christophe ;
Pelle, Julien ;
Beaubert, Francois ;
Harmand, Souad ;
Moreau, Olivier .
IEEE TRANSACTIONS ON POWER DELIVERY, 2017, 32 (06) :2453-2461
[8]  
Carr, CARR
[9]  
Chambers J.R., 2010, Modeling flight: the role of dynamically scaled free-flight models in support of NASA's aerospace programs
[10]  
CigreWorking Group 08 of Study Committee 21, 1992, ELECTRA, V143, P39