Performance evaluation of ductless personalized ventilation in comparison with desk fans using numerical simulations

被引:16
作者
Alsaad, Hayder [1 ]
Voelker, Conrad [1 ]
机构
[1] Bauhaus Univ Weimar, Dept Bldg Phys, Coudraystr 11A, D-99423 Weimar, Germany
关键词
computational fluid dynamics; desk fan; ductless personalized ventilation; IAQ; thermal comfort; thermal sensation; PERCEIVED AIR-QUALITY; THERMAL COMFORT; SBS SYMPTOMS; CFD; FLOW; ENVIRONMENT; CONJUNCTION; OFFICE; SYSTEM;
D O I
10.1111/ina.12672
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The performance of ductless personalized ventilation (DPV) was compared to the performance of a typical desk fan since they are both stand-alone systems that allow the users to personalize their indoor environment. The two systems were evaluated using a validated computational fluid dynamics (CFD) model of an office room occupied by two users. To investigate the impact of DPV and the fan on the inhaled air quality, two types of contamination sources were modeled in the domain: an active source and a passive source. Additionally, the influence of the compared systems on thermal comfort was assessed using the coupling of CFD with the comfort model developed by the University of California, Berkeley (UCB model). Results indicated that DPV performed generally better than the desk fan. It provided better thermal comfort and showed a superior performance in removing the exhaled contaminants. However, the desk fan performed better in removing the contaminants emitted from a passive source near the floor level. This indicates that the performance of DPV and desk fans depends highly on the location of the contamination source. Moreover, the simulations showed that both systems increased the spread of exhaled contamination when used by the source occupant.
引用
收藏
页码:776 / 789
页数:14
相关论文
共 52 条
[1]  
Abbas T, 1999, DISPLACEMENT VENTILA
[2]   Qualitative evaluation of the flow supplied by personalized ventilation using schlieren imaging and thermography [J].
Alsaad, Hayder ;
Voelker, Conrad .
BUILDING AND ENVIRONMENT, 2020, 167
[3]   Performance assessment of a ductless personalized ventilation system using a validated CFD model [J].
Alsaad, Hayder ;
Voelker, Conrad .
JOURNAL OF BUILDING PERFORMANCE SIMULATION, 2018, 11 (06) :689-704
[4]  
[Anonymous], 2017 ASHRAE Handbook - Fundamentals
[5]  
[Anonymous], 2005, Ergonomics of the thermal environment _ Analytical determination and interpretation of thermal comfort using calculation of the PMV and PPD indices and local thermal comfort criteria
[6]  
[Anonymous], 2007, CRIT IND ENV INCL TH
[7]  
ANSYS, 2015, ANSYSR AC RES REL 16
[8]   Coaxial personalized ventilation system and window performance for human thermal comfort in asymmetrical environment [J].
Antoun, Sylvie ;
Ghaddar, Nesreen ;
Ghali, Kamel .
ENERGY AND BUILDINGS, 2016, 111 :253-266
[9]   A study of occupant cooling by personally controlled air movement [J].
Arens, E ;
Xu, TF ;
Miura, K ;
Hui, Z ;
Fountain, M ;
Bauman, F .
ENERGY AND BUILDINGS, 1998, 27 (01) :45-59
[10]  
ASHRAE, 2013, 55 ANSIASHRAE