Numerical modelling and parametric study of an air-cooled desiccant coated cross-flow heat exchanger

被引:30
作者
Liu, Lin [1 ,2 ]
Zeng, Tao [1 ]
Huang, Hongyu [1 ]
Kubota, Mitsuhiro [3 ]
Kobayashi, Noriyuki [3 ]
He, Zhaohong [1 ]
Li, Jun [3 ]
Deng, Lisheng [1 ,4 ]
Li, Xing [1 ]
Feng, Yuheng [4 ,5 ]
Yan, Kai [5 ]
机构
[1] Chinese Acad Sci, Guangzhou Inst Energy Convers, Key Lab Renewable Energy, Guangdong Prov Key Lab New & Renewable Energy Res, 2 Nengyuan Rd, Guangzhou 510640, Peoples R China
[2] Univ Chinese Acad Sci, Beijing 100049, Peoples R China
[3] Nagoya Univ, Chikusa Ku, Furo Cho, Nagoya, Aichi 4648603, Japan
[4] Tongji Univ, Thermal & Environm Engn Inst, 1239 Siping Rd, Shanghai 200092, Peoples R China
[5] Shanghai Boiler Works Co Ltd, Shanghai 200245, Peoples R China
关键词
Numerical modeling; Solid dehumidification; Cross-flow heat exchanger; Desiccant coated heat exchanger; Air conditioning; PERFORMANCE; DEHUMIDIFICATION; WHEEL; MASS;
D O I
10.1016/j.applthermaleng.2020.114901
中图分类号
O414.1 [热力学];
学科分类号
摘要
Air-cooled desiccant coated cross-flow heat exchanger (DCCFHE) system provides a simple and effective approach to improve dehumidification performance by using cooling air to remove adsorption heat during adsorption process. In this study, a novel numerical model validated by experimental data was established to predict the performance of a conventional silica gel DCCFHE system. The fin efficiency, as a variable due to the release of adsorption heat, was taken into account in the model. Parametric study for various air velocity and structural parameters was conducted to reveal their effects on the dehumidification performance. Results show that the smaller process air velocity is conducive to improve dehumidification performance, but the performance increases with the increase in cooling air velocity. Compared to the operation case without cooling air, the moisture removal capacity and dehumidification coefficient of performance can obtain about 35% improvement at the cooling air velocity of 1 m/s. The results also indicate that thicker desiccant layer thickness and smaller fin pitch improve moisture removal capacity and dehumidification coefficient of performance but result in greater total pressure drop Delta P, while the performance is insensible to fin thickness and fin height. Besides, effect of heat transfer performance in dehumidification and cooling sides on dehumidification performance was also analyzed. It was found that the heat transfer performance in dehumidification side is the dominant factor affecting dehumidification performance.
引用
收藏
页数:16
相关论文
共 29 条
  • [21] Evaluation of a dehumidifier with adsorbent coated heat exchangers for tropical climate operations
    Oh, Seung Jin
    Ng, Kim Choon
    Chun, Wongee
    Chua, Kian Jon Ernest
    [J]. ENERGY, 2017, 137 : 441 - 448
  • [22] Shah R.K., 2002, Fundamentals of Heat Exchanger Design, V1st
  • [23] DIFFUSION ON SURFACES .2. CORRELATION OF DIFFUSIVITIES OF PHYSICALLY AND CHEMICALLY ADSORBED SPECIES
    SLADEK, KJ
    GILLILAND, ER
    BADDOUR, RF
    [J]. INDUSTRIAL & ENGINEERING CHEMISTRY FUNDAMENTALS, 1974, 13 (02): : 100 - 105
  • [24] Analysis of heat and mass transfer in porous sorbents used in rotary regenerators
    Sphaier, LA
    Worek, WM
    [J]. INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2004, 47 (14-16) : 3415 - 3430
  • [25] Recent developments in solid desiccant coated heat exchangers - A review
    Vivekh, P.
    Kumja, M.
    Bui, D. T.
    Chua, K. J.
    [J]. APPLIED ENERGY, 2018, 229 : 778 - 803
  • [26] Wang F., 2004, ASHRAE T, V110
  • [27] PERFORMANCE OF A CROSS-COOLED DESICCANT DEHUMIDIFIER PROTOTYPE
    WOREK, WM
    LAVAN, Z
    [J]. JOURNAL OF SOLAR ENERGY ENGINEERING-TRANSACTIONS OF THE ASME, 1982, 104 (03): : 187 - 196
  • [28] Study of a new modified cross-cooled compact solid desiccant dehumidifier
    Yuan Weixing
    Zheng Yi
    Liu Xiaoru
    Yuan Xiugan
    [J]. APPLIED THERMAL ENGINEERING, 2008, 28 (17-18) : 2257 - 2266
  • [29] Performance comparisons of desiccant wheels for air dehumidification and enthalpy recovery
    Zhang, LZ
    Niu, JL
    [J]. APPLIED THERMAL ENGINEERING, 2002, 22 (12) : 1347 - 1367