Numerical modelling and parametric study of an air-cooled desiccant coated cross-flow heat exchanger

被引:30
作者
Liu, Lin [1 ,2 ]
Zeng, Tao [1 ]
Huang, Hongyu [1 ]
Kubota, Mitsuhiro [3 ]
Kobayashi, Noriyuki [3 ]
He, Zhaohong [1 ]
Li, Jun [3 ]
Deng, Lisheng [1 ,4 ]
Li, Xing [1 ]
Feng, Yuheng [4 ,5 ]
Yan, Kai [5 ]
机构
[1] Chinese Acad Sci, Guangzhou Inst Energy Convers, Key Lab Renewable Energy, Guangdong Prov Key Lab New & Renewable Energy Res, 2 Nengyuan Rd, Guangzhou 510640, Peoples R China
[2] Univ Chinese Acad Sci, Beijing 100049, Peoples R China
[3] Nagoya Univ, Chikusa Ku, Furo Cho, Nagoya, Aichi 4648603, Japan
[4] Tongji Univ, Thermal & Environm Engn Inst, 1239 Siping Rd, Shanghai 200092, Peoples R China
[5] Shanghai Boiler Works Co Ltd, Shanghai 200245, Peoples R China
关键词
Numerical modeling; Solid dehumidification; Cross-flow heat exchanger; Desiccant coated heat exchanger; Air conditioning; PERFORMANCE; DEHUMIDIFICATION; WHEEL; MASS;
D O I
10.1016/j.applthermaleng.2020.114901
中图分类号
O414.1 [热力学];
学科分类号
摘要
Air-cooled desiccant coated cross-flow heat exchanger (DCCFHE) system provides a simple and effective approach to improve dehumidification performance by using cooling air to remove adsorption heat during adsorption process. In this study, a novel numerical model validated by experimental data was established to predict the performance of a conventional silica gel DCCFHE system. The fin efficiency, as a variable due to the release of adsorption heat, was taken into account in the model. Parametric study for various air velocity and structural parameters was conducted to reveal their effects on the dehumidification performance. Results show that the smaller process air velocity is conducive to improve dehumidification performance, but the performance increases with the increase in cooling air velocity. Compared to the operation case without cooling air, the moisture removal capacity and dehumidification coefficient of performance can obtain about 35% improvement at the cooling air velocity of 1 m/s. The results also indicate that thicker desiccant layer thickness and smaller fin pitch improve moisture removal capacity and dehumidification coefficient of performance but result in greater total pressure drop Delta P, while the performance is insensible to fin thickness and fin height. Besides, effect of heat transfer performance in dehumidification and cooling sides on dehumidification performance was also analyzed. It was found that the heat transfer performance in dehumidification side is the dominant factor affecting dehumidification performance.
引用
收藏
页数:16
相关论文
共 29 条
  • [1] A. H. F. ASHRAE, 1997, AM SOC HEAT REFR AIR
  • [2] Numerical modelling of flow and coupled mass and heat transfer in an adsorption process
    Cheng, Dang
    Peters, E. A. J. F.
    Kuipers, J. A. M.
    [J]. CHEMICAL ENGINEERING SCIENCE, 2016, 152 : 413 - 425
  • [3] SORPTION EQUILIBRIUM OF A SOLID DESICCANT FELT AND THE EFFECT OF SORPTION PROPERTIES ON A COOLED-BED DESICCANT COOLING SYSTEM
    DINI, S
    WOREK, WM
    [J]. JOURNAL OF HEAT RECOVERY SYSTEMS, 1986, 6 (02): : 151 - 167
  • [4] The role of the thermally activated desiccant cooling technologies in the issue of energy and environment
    Enteria, Napoleon
    Mizutani, Kunio
    [J]. RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2011, 15 (04) : 2095 - 2122
  • [5] Simulation investigation on solar powered desiccant coated heat exchanger cooling system
    Ge, T. S.
    Dai, Y. J.
    Li, Y.
    Wang, R. Z.
    [J]. APPLIED ENERGY, 2012, 93 : 532 - 540
  • [6] Performance study of silica gel coated fin-tube heat exchanger cooling system based on a developed mathematical model
    Ge, T. S.
    Dai, Y. J.
    Wang, R. Z.
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2011, 52 (06) : 2329 - 2338
  • [7] Experimental comparison and analysis on silica gel and polymer coated fin-tube heat exchangers
    Ge, T. S.
    Dai, Y. J.
    Wang, R. Z.
    Peng, Z. Z.
    [J]. ENERGY, 2010, 35 (07) : 2893 - 2900
  • [8] A mathematical model for predicting the performance of a compound desiccant wheel (A model of compound desiccant wheel)
    Ge, T. S.
    Ziegler, F.
    Wang, R. Z.
    [J]. APPLIED THERMAL ENGINEERING, 2010, 30 (8-9) : 1005 - 1015
  • [9] Mathematical modeling and performance evaluation of a desiccant coated fin-tube heat exchanger
    Jagirdar, Mrinal
    Lee, Poh Seng
    [J]. APPLIED ENERGY, 2018, 212 : 401 - 415
  • [10] Performance analysis of desiccant dehumidification systems driven by low-grade heat source
    Jeong, Jongsoo
    Yamaguchi, Seiichi
    Saito, Kiyoshi
    Kawai, Sunao
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2011, 34 (04): : 928 - 945