A Novel Method for Fault Location of Transmission Lines by Wide-Area Voltage Measurements Considering Measurement Errors

被引:54
作者
Dobakhshari, A. Salehi [1 ]
Ranjbar, A. M. [1 ]
机构
[1] Sharif Univ Technol, Dept Elect Engn, Tehran 1136511155, Iran
关键词
Bus impedance matrix; fault location; least squares method; measurement errors; 3-TERMINAL LINES; ALGORITHM;
D O I
10.1109/TSG.2014.2322977
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Smart transmission grids are intended to utilize various measurements for enhanced operation. In particular, synchronized phasor measurements have found many applications in this context. This paper presents a linear weighted least-squares (WLS) method for fault location estimation of transmission lines by synchronized voltage measurements. The measurements may be taken from the faulted line terminals or buses far from the faulted line. The circuit equations of the network are used to find the transfer function between the fault location and each voltage measurement. Next, two auxiliary variables are defined to transform the nonlinear fault location estimation problem into a linear WLS problem. A closed-form solution is then obtained for fault location. The use of multiple measurements provides the opportunity of identifying erroneous measurements by a statistical test. The linearity of the problem expedites both estimation and identification procedures. Moreover, the method requires neither to classify the fault type nor to estimate the fault resistance. Furthermore, transmission lines are modeled by distributed parameters so that the method can be applicable to long lines. Electromagnetic transient simulations for 9-bus and 22-bus test systems reveal accurate fault location estimation, regardless of fault type and resistance, as well as successful identification of measurement errors.
引用
收藏
页码:874 / 884
页数:11
相关论文
共 34 条
[1]   DEVELOPMENT OF A NEW FAULT LOCATION SYSTEM FOR MULTITERMINAL SINGLE TRANSMISSION-LINES [J].
ABE, M ;
OTSUZUKI, N .
IEEE TRANSACTIONS ON POWER DELIVERY, 1995, 10 (01) :159-168
[2]   A PRACTICAL APPROACH TO ACCURATE FAULT LOCATION ON EXTRA-HIGH-VOLTAGE TEED FEEDERS [J].
AGGARWAL, RK ;
COURY, DV ;
JOHNS, AT ;
KALAM, A ;
NILSSON, SL .
IEEE TRANSACTIONS ON POWER DELIVERY, 1993, 8 (03) :874-883
[3]  
[Anonymous], 2004, Power System State Estimation Theory and Implementation
[4]   Optimal Integration of Phasor Measurement Units in Power Systems Considering Conventional Measurements [J].
Azizi, S. ;
Gharehpetian, G. B. ;
Dobakhshari, A. Salehi .
IEEE TRANSACTIONS ON SMART GRID, 2013, 4 (02) :1113-1121
[5]  
Azizi S., 2014, IEEE T POWER DEL
[6]   Optimal PMU Placement by an Equivalent Linear Formulation for Exhaustive Search [J].
Azizi, Sadegh ;
Dobakhshari, Ahmad Salehi ;
Sarmadi, S. Arash Nezam ;
Ranjbar, Ali Mohammad .
IEEE TRANSACTIONS ON SMART GRID, 2012, 3 (01) :174-182
[7]   Fault location on a transmission line using synchronized voltage measurements [J].
Brahma, SM ;
Girgis, AA .
IEEE TRANSACTIONS ON POWER DELIVERY, 2004, 19 (04) :1619-1622
[8]   A Simple Synchrophasor Estimation Algorithm Considering IEEE Standard C37.118.1-2011 and Protection Requirements [J].
Das, Sarasij ;
Sidhu, Tarlochan .
IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 2013, 62 (10) :2704-2715
[9]  
Eriksson L., 1985, IEEE T POWER APP SYS, VPAS-104, P423
[10]   Fault location using voltage measurements [J].
Galijasevic, Z ;
Abur, A .
IEEE TRANSACTIONS ON POWER DELIVERY, 2002, 17 (02) :441-445