Asymmetric relay autotuning - Practical features for industrial use

被引:48
作者
Berner, Josefin [1 ]
Hagglund, Tore [1 ]
Astrom, Karl Johan [1 ]
机构
[1] Lund Univ, Dept Automat Control, S-22100 Lund, Sweden
关键词
Asymmetric relay autotuning; PID control; Practical features; Industrial experiment; Air handling unit; STATIC LOAD DISTURBANCES; PARAMETER-ESTIMATION; FEEDBACK; IDENTIFICATION;
D O I
10.1016/j.conengprac.2016.05.017
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
The relay autotuner provides a simple way of finding PID controller parameters. Even though relay autotuning is much investigated in the literature, the practical aspects are not that well-documented. In this paper an asymmetric relay autotuner with features such as a startup procedure and adaptive relay amplitudes is proposed. Parameter choices and handling of noise, disturbances, start in non-steady state and other possible error sources are discussed. The autotuner is implemented and tested on an industrial air handling unit to show its use in practice. The experiments show good results, and prove that the proposed simple autotuner is well-suited for industrial use. But the experiments also enlighten possible error sources and remaining problems. (C) 2016 Elsevier Ltd. All rights reserved.
引用
收藏
页码:231 / 245
页数:15
相关论文
共 20 条
[11]   Parameter estimation from relay autotuning with asymmetric limit cycle data [J].
Kaya, I ;
Atherton, DP .
JOURNAL OF PROCESS CONTROL, 2001, 11 (04) :429-439
[12]   AN IMPROVED AUTOTUNE IDENTIFICATION METHOD [J].
LI, W ;
ESKINAT, E ;
LUYBEN, WL .
INDUSTRIAL & ENGINEERING CHEMISTRY RESEARCH, 1991, 30 (07) :1530-1541
[13]   Relay feedback: A complete analysis for first-order systems [J].
Lin, C ;
Wang, QG ;
Lee, TH .
INDUSTRIAL & ENGINEERING CHEMISTRY RESEARCH, 2004, 43 (26) :8400-8402
[14]   A tutorial review on process identification from step or relay feedback test [J].
Liu, Tao ;
Wang, Qing-Guo ;
Huang, Hsiao-Ping .
JOURNAL OF PROCESS CONTROL, 2013, 23 (10) :1597-1623
[16]   Improved relay auto-tuning with static load disturbance [J].
Park, JH ;
Sung, SW ;
Lee, IB .
AUTOMATICA, 1997, 33 (04) :711-715
[17]   Autotune identification under load disturbance [J].
Shen, SH ;
Wu, JS ;
Yu, CC .
INDUSTRIAL & ENGINEERING CHEMISTRY RESEARCH, 1996, 35 (05) :1642-1651
[18]   Use of biased-relay feedback for system identification [J].
Shen, SH ;
Wu, JS ;
Yu, CC .
AICHE JOURNAL, 1996, 42 (04) :1174-1180
[19]   Relay feedback method under large static disturbances [J].
Sung, SW ;
Lee, J .
AUTOMATICA, 2006, 42 (02) :353-356
[20]  
Theorin A., 2015, P 2015 IEEE INT C AU, P874