Adsorption chiller operation by recovering low-temperature heat from building integrated photovoltaic thermal collectors: Modelling and simulation

被引:75
作者
Buonomano, Annamaria [1 ]
Calise, Francesco [1 ]
Palombo, Adolfo [1 ]
Vicidomini, Maria [1 ]
机构
[1] Univ Naples Federico II, Dept Ind Engn, Ple Tecchio 80, I-80125 Naples, Italy
关键词
Dynamic simulation; Energy-economic and environmental analysis; Solar cooling; Adsorption chiller; Electricity storage; Building Integrated PhotoVoltaic Thermal (BIPVT) collectors; ENERGY-STORAGE SYSTEM; SOLAR COOLING SYSTEMS; THERMOECONOMIC OPTIMIZATION; CLIMATIC CONDITIONS; DYNAMIC SIMULATION; ECONOMIC-ANALYSIS; PERFORMANCE; DRIVEN; IDENTIFICATION; REFRIGERATION;
D O I
10.1016/j.enconman.2017.05.005
中图分类号
O414.1 [热力学];
学科分类号
摘要
This work focuses on a dynamic simulation model for the energy, economic and environmental analysis of an innovative polygenerative system layout based on a building integrated photovoltaic thermal system coupled to an adsorption chiller and to an electricity storage system. The thermal energy of building integrated photovoltaic thermal collectors is exploited in order to produce solar space heating and cooling and domestic hot water. Auxiliary electric air-to-water heat pumps/chillers and a gas-fired condensation boiler are included in the system model in order to integrate the demands of heating, cooling and domestic hot water production. The electricity produced by building integrated photovoltaic thermal collectors is used to satisfy the building needs. The eventual extra-production is delivered to the grid or stored in lead-acid batteries. By means of the developed dynamic simulation model (implemented in TRNSYS environment) the energy system performance on the whole building can be analysed in terms of heating/cooling energy, electricity and domestic hot water demands. In particular, both the passive and active energy effects of the investigated collectors can be assessed. The model includes a suitable tool for the comparison of the innovative system layout vs. traditional reference building-plant systems. For energy, economic and environmental impact optimization purposes, sensitivity analyses can be performed by varying the main system design parameters with respect to the value of reference case ones. In order to show the potentiality of the developed simulation model, several new case studies are developed. They refer to a 3-floor office building located in four different Italian weather zones. Simulation results show that the obtained SPBs, the primary energy saving for electricity and domestic hot water production, and the equivalent carbon dioxide avoided emissions range between 10.6-11.3 years, 58.5-68.8% and 763-90.2%, respectively. (C) 2017 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1019 / 1036
页数:18
相关论文
共 10 条
  • [1] Modelling and experimental investigation of an adsorption chiller using low-temperature heat from cogeneration
    Chorowski, Maciej
    Pyrka, Piotr
    ENERGY, 2015, 92 : 221 - 229
  • [2] Performance evaluation of a low-temperature waste heat driven multi-bed adsorption chiller
    Saha, BB
    Koyama, S
    Lee, JB
    Kuwahara, K
    Alam, KCA
    Hamamoto, Y
    Akisawa, A
    Kashiwagi, T
    INTERNATIONAL JOURNAL OF MULTIPHASE FLOW, 2003, 29 (08) : 1249 - 1263
  • [3] Solar heating and cooling systems by absorption and adsorption chillers driven by stationary and concentrating photovoltaic/thermal solar collectors: Modelling and simulation
    Buonomano, Annamaria
    Calise, Francesco
    Palombo, Adolfo
    RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2018, 82 : 1874 - 1908
  • [4] Dynamic simulation of a trigeneration system using an absorption cooling system and building integrated photovoltaic thermal solar collectors
    Jalalizadeh, Mohammad
    Fayaz, Rima
    Delfani, Shahram
    Mosleh, Hassan Jafari
    Karami, Maryam
    JOURNAL OF BUILDING ENGINEERING, 2021, 43
  • [5] Dynamic simulation and exergy analysis of adsorption chiller powered by low-grade waste heat from a fuel-cell system: Effect of multibed configuration and time constant
    Naseem, Mujahid
    Son, Namin
    Lee, Young Duk
    ENERGY CONVERSION AND MANAGEMENT, 2023, 293
  • [6] Modelling of photovoltaic-thermal collectors for the provision of electricity and low temperature heat-Comparison of different flow rate control approaches to optimize the electrical yield
    Christ, Daniel
    Kaltschmitt, Martin
    RENEWABLE ENERGY FOCUS, 2021, 37 : 1 - 13
  • [7] Multiple-inlet Building Integrated Photovoltaic/Thermal system modelling under varying wind and temperature conditions
    Rounis, Efstratios Dimitrios
    Athienitis, Andreas K.
    Stathopoulos, Theodore
    SOLAR ENERGY, 2016, 139 : 157 - 170
  • [8] Operation and grid interaction modeling of a house with a building integrated photovoltaic thermal (BIPV/T) system coupled to an air-source heat pump
    Dumoulin, Remi
    Rounis, Efstratios Dimitrios
    Athienitis, Andreas
    SCIENCE AND TECHNOLOGY FOR THE BUILT ENVIRONMENT, 2021, 27 (09) : 1311 - 1329
  • [9] Recommendations for Running a Tandem of Adsorption Chillers Connected in Series and Powered by Low-Temperature Heat from District Heating Network
    Nalepa, Bartlomiej
    Halon, Tomasz
    ENERGIES, 2021, 14 (16)
  • [10] Removal of dioxins from municipal solid waste incineration fly ash by low-temperature thermal treatment: Laboratory simulation of degradation and ash discharge stages
    Li, Weishi
    Li, Li
    Wen, Zhuoyu
    Yan, Dahai
    Liu, Meijia
    Huang, Qifei
    Zhu, Zhanheng
    WASTE MANAGEMENT, 2023, 168 : 45 - 53