Heat Transfer Enhancement by Perforated and Louvred Fin Heat Exchangers

被引:6
作者
Altwieb, Miftah [1 ]
Mishra, Rakesh [2 ]
Aliyu, Aliyu M. [2 ]
Kubiak, Krzysztof J. [3 ]
机构
[1] Univ Gharyan, Dept Mech & Ind Engn, Gharyan 010101, Libya
[2] Univ Huddersfield, Sch Comp & Engn, Huddersfield HD1 3DH, W Yorkshire, England
[3] Univ Leeds, Sch Mech Engn, Leeds LS2 9JT, W Yorkshire, England
关键词
heat exchanger; heat transfer; louvred fins; heat transfer effectiveness; Fanning friction factor; Colburn factor; TUBE; PERFORMANCE; FLOW;
D O I
10.3390/en15020400
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Multi-tube multi-fin heat exchangers are extensively used in various industries. In the current work, detailed experimental investigations were carried out to establish the flow/heat transfer characteristics in three distinct heat exchanger geometries. A novel perforated plain fin design was developed, and its performance was evaluated against standard plain and louvred fins designs. Experimental setups were designed, and the tests were carefully carried out which enabled quantification of the heat transfer and pressure drop characteristics. In the experiments the average velocity of air was varied in the range of 0.7 m/s to 4 m/s corresponding to Reynolds numbers of 600 to 2650. The water side flow rates in the tubes were kept at 0.12, 0.18, 0.24, 0.3, and 0.36 m(3)/h corresponding to Reynolds numbers between 6000 and 30,000. It was found that the louvred fins produced the highest heat transfer rate due to the availability of higher surface area, but it also produced the highest pressure drops. Conversely, while the new perforated design produced a slightly higher pressure drop than the plain fin design, it gave a higher value of heat transfer rate than the plain fin especially at the lower liquid flow rates. Specifically, the louvred fin gave consistently high pressure drops, up to 3 to 4 times more than the plain and perforated models at 4 m/s air flow, however, the heat transfer enhancement was only about 11% and 13% over the perforated and plain fin models, respectively. The mean heat transfer rate and pressure drops were used to calculate the Colburn and Fanning friction factors. Two novel semiempirical relationships were derived for the heat exchanger's Fanning and Colburn factors as functions of the non-dimensional fin surface area and the Reynolds number. It was demonstrated that the Colburn and Fanning factors were predicted by the new correlations to within +/- 15% of the experiments.
引用
收藏
页数:16
相关论文
共 26 条
[1]   Performance characteristics correlation for round tube and plate finned heat exchangers [J].
Abu Madi, M ;
Johns, RA ;
Heikal, MR .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1998, 21 (07) :507-517
[2]  
Altwieb M.O., 2016, P 6 INT 43 NATL C FL, P1
[3]   A new three-dimensional CFD model for efficiency optimisation of fluid-to-air multi-fin heat exchanger [J].
Altwieb, Miftah ;
Kubiak, Krzysztof J. ;
Aliyu, Aliyu M. ;
Mishra, Rakesh .
THERMAL SCIENCE AND ENGINEERING PROGRESS, 2020, 19
[4]  
[Anonymous], 2013, Heat Exchanger Design Handbook
[5]  
[Anonymous], 2013, HVAC Design Manual for Hospitals and Clinics, V2nd
[6]  
[Anonymous], TFI COBRA PROBE 2021
[7]   Effects of the geometrical features of flow paths on the flow capacity of a control valve trim [J].
Asim, Taimoor ;
Mishra, Rakesh ;
Oliveira, Antonio ;
Charlton, Matthew .
JOURNAL OF PETROLEUM SCIENCE AND ENGINEERING, 2019, 172 :124-138
[8]   CFD based investigations for the design of severe service control valves used in energy systems [J].
Asim, Taimoor ;
Charlton, Matthew ;
Mishra, Rakesh .
ENERGY CONVERSION AND MANAGEMENT, 2017, 153 :288-303
[9]  
Colburn AP, 1933, T AM INST CHEM ENG, V29, P174