High-impedance fault detection in electrical power distribution systems using moving sum approach

被引:47
|
作者
Sarwagya, Kumari [1 ]
De, Sourav [1 ]
Nayak, Paresh Kumar [1 ]
机构
[1] Indian Inst Technol, Indian Sch Mines, Dept Elect Engn, Dhanbad 826004, Bihar, India
关键词
ENHANCED PROTECTION SCHEME; ARCING FAULT; DISTRIBUTION FEEDERS; MV NETWORKS; LOCATION; TRANSFORM; BEHAVIOR;
D O I
10.1049/iet-smt.2017.0231
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
High-impedance faults (HIFs) in electrical power distribution systems produce a very random, non-linear and low-magnitude fault current. The conventional overcurrent (OC) relaying-based distribution system protection schemes find difficulty in detecting such low-current HIFs. In this study, a simple two criteria-based protection scheme is proposed for detection and isolation of HIFs in multi-feeder radial distribution systems. It utilises one-cycle sum of superimposed components of residual voltage for HIF detection and the maximum value of one-cycle sum of superimposed components of negative-sequence current for faulted feeder identification. The performance of the proposed scheme is evaluated for a wide variety of possible test cases by generating data through power systems computer-aided design/electro-magnetic transient design and control software. Results clearly show that the proposed scheme can assist conventional OC relay for detection and isolation of HIFs in distribution systems with any grounding connections in a more reliable and faster way.
引用
收藏
页码:1 / 8
页数:8
相关论文
共 50 条
  • [1] High-impedance fault detection in power distribution grid systems based on support vector machine approach
    Ahmadi, Ali
    Aghajari, Ebrahim
    Zangeneh, Mehdi
    ELECTRICAL ENGINEERING, 2022, 104 (05) : 3659 - 3672
  • [2] Application of signal processing techniques and intelligent classifiers for high-impedance fault detection in ensuring the reliable operation of power distribution systems
    Varghese, P. Rini
    Subathra, M. S. P.
    George, S. Thomas
    Kumar, Nallapaneni Manoj
    Suviseshamuthu, Easter Selvan
    Deb, Sanchari
    FRONTIERS IN ENERGY RESEARCH, 2023, 11
  • [3] Detection of High Impedance Fault in Power Distribution Systems Using Mathematical Morphology
    Gautam, Suresh
    Brahma, Sukumar M.
    IEEE TRANSACTIONS ON POWER SYSTEMS, 2013, 28 (02) : 1226 - 1234
  • [4] High-impedance fault detection and classification in power system distribution networks using morphological fault detector algorithm
    Kavi, Moses
    Mishra, Yateendra
    Vilathgamuwa, Mahinda D.
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2018, 12 (15) : 3699 - 3710
  • [5] A Novel High-Impedance Fault Detection Technique in Smart Active Distribution Systems
    Dubey, Kartika
    Jena, Premalata
    IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2024, 71 (05) : 4861 - 4872
  • [6] Practical high-impedance fault detection on distribution feeders
    Benner, CL
    Russell, BD
    IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1997, 33 (03) : 635 - 640
  • [7] High-impedance faults in power distribution systems: A narrative of the field's developments
    Gomes, D. P. S.
    Ozansoy, C.
    ISA TRANSACTIONS, 2021, 118 (118) : 15 - 34
  • [8] Evidential reasoning based approach to high impedance fault detection in power distribution systems
    Soheili, Adel
    Sadeh, Javad
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2017, 11 (05) : 1325 - 1336
  • [9] High-Impedance Fault Identification on Distribution Networks
    Santos, W. C.
    Lopes, F. V.
    Brito, N. S. D.
    Souza, B. A.
    IEEE TRANSACTIONS ON POWER DELIVERY, 2017, 32 (01) : 23 - 32
  • [10] High-Impedance Fault Detection in the Distribution Network Using the Time-Frequency-Based Algorithm
    Ghaderi, Amin
    Mohammadpour, Hossein Ali
    Ginn, Herbert L., II
    Shin, Yong-June
    IEEE TRANSACTIONS ON POWER DELIVERY, 2015, 30 (03) : 1260 - 1268