共 50 条
High-impedance fault detection in electrical power distribution systems using moving sum approach
被引:47
|作者:
Sarwagya, Kumari
[1
]
De, Sourav
[1
]
Nayak, Paresh Kumar
[1
]
机构:
[1] Indian Inst Technol, Indian Sch Mines, Dept Elect Engn, Dhanbad 826004, Bihar, India
关键词:
ENHANCED PROTECTION SCHEME;
ARCING FAULT;
DISTRIBUTION FEEDERS;
MV NETWORKS;
LOCATION;
TRANSFORM;
BEHAVIOR;
D O I:
10.1049/iet-smt.2017.0231
中图分类号:
TM [电工技术];
TN [电子技术、通信技术];
学科分类号:
0808 ;
0809 ;
摘要:
High-impedance faults (HIFs) in electrical power distribution systems produce a very random, non-linear and low-magnitude fault current. The conventional overcurrent (OC) relaying-based distribution system protection schemes find difficulty in detecting such low-current HIFs. In this study, a simple two criteria-based protection scheme is proposed for detection and isolation of HIFs in multi-feeder radial distribution systems. It utilises one-cycle sum of superimposed components of residual voltage for HIF detection and the maximum value of one-cycle sum of superimposed components of negative-sequence current for faulted feeder identification. The performance of the proposed scheme is evaluated for a wide variety of possible test cases by generating data through power systems computer-aided design/electro-magnetic transient design and control software. Results clearly show that the proposed scheme can assist conventional OC relay for detection and isolation of HIFs in distribution systems with any grounding connections in a more reliable and faster way.
引用
收藏
页码:1 / 8
页数:8
相关论文