Rotor inertia adaptive control and inertia matching strategy based on parallel virtual synchronous generators system

被引:26
作者
Shi, Kai [1 ]
Chen, Cheng [1 ]
Sun, Yuxin [1 ]
Xu, Peifeng [1 ]
Yang, Yongheng [2 ]
Blaabjerg, Frede [2 ]
机构
[1] Jiangsu Univ, Sch Elect & Informat Engn, Zhenjiang 212013, Jiangsu, Peoples R China
[2] Aalborg Univ, Dept Energy Technol, DK-9220 Aalborg, Denmark
基金
国家重点研发计划; 中国国家自然科学基金;
关键词
damping; synchronous generators; adaptive control; power generation control; rotors; optimisation; rotor inertia adaptive control; inertia matching strategy; parallel virtual synchronous generators system; active power oscillations; frequency fluctuations; virtual synchronous generator systems; fixed rotor inertia; damping coefficients; optimisation control strategy; power oscillation; small-signal model; parallel VSG systems; output active power; parameter optimisation control; self-adjusting inertia; virtual rotor electrical angular velocity; dynamic state performance; steady-state performance; equivalent synchronous generator; virtual inertia matching method; control method; frequency support; load power;
D O I
10.1049/iet-gtd.2019.1394
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Active power oscillations and frequency fluctuations appear simultaneously in virtual synchronous generator (VSG) systems with fixed rotor inertia and damping coefficients. Thus, an optimisation control strategy to self-adjust the parameters is proposed in this study to suppress the power oscillations and frequency fluctuations. A small-signal model of parallel VSG systems is established, and the impact of rotor inertia and damping coefficients on the output active power is analysed. Then, the parameter optimisation control for the self-adjusting inertia and damping coefficients is introduced according to the rate of change and the deviation of virtual rotor electrical angular velocity. Notably, the changes and deviations are limited in a range to ensure the dynamic and steady-state performance of the system. Based on the principle of the equivalent synchronous generator, a virtual inertia matching method for parallel VSG systems is accordingly obtained. The feasibility of the proposed control method is verified by extensive simulations. The results confirm that this method can not only suppress the power oscillation in the transient connection of the VSGs to the AC bus, but also improve the frequency support. In turn, it ensures that the load power is proportionally distributed among the VSGs.
引用
收藏
页码:1854 / 1861
页数:8
相关论文
共 25 条
[1]   Stability Assessment and Optimization Methods for Microgrid With Multiple VSG Units [J].
Alipoor, Jaber ;
Miura, Yushi ;
Ise, Toshifumi .
IEEE TRANSACTIONS ON SMART GRID, 2018, 9 (02) :1462-1471
[2]  
Bo L, 2017, IEEE IND ELEC, P4116, DOI 10.1109/IECON.2017.8216706
[3]  
[程冲 Cheng Chong], 2015, [电力系统自动化, Automation of Electric Power Systems], V39, P82
[4]   A Self-Adjusting Droop Control Strategy to Improve Reactive Power Sharing in Islanded Microgrid [J].
Dheer, Dharmendra Kumar ;
Gupta, Yusuf ;
Doolla, Suryanarayana .
IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, 2020, 11 (03) :1624-1635
[5]  
Du Yan, 2013, Proceedings of the CSEE, V33, P67
[6]   Distributed Control of Low-Voltage Resistive AC Microgrids [J].
Golsorkhi, Mohammad Sadegh ;
Shafiee, Qobad ;
Lu, Dylan Dah-Chuan ;
Guerrero, Josep M. .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 2019, 34 (02) :573-584
[7]  
Li G., 2007, POWER SYSTEM TRANSIE
[8]   Adaptive Virtual Inertia Control Strategy of VSG for Micro-Grid Based on Improved Bang-Bang Control Strategy [J].
Li, Jin ;
Wen, Buying ;
Wang, Huaiyuan .
IEEE ACCESS, 2019, 7 :39509-39514
[9]  
Lin KW, 2017, CHIN CONTR CONF, P6453, DOI 10.23919/ChiCC.2017.8028382
[10]  
Lu Zhipeng, 2014, Proceedings of the CSEE, V34, P2591