Investigation of a cascaded H-bridge photovoltaic inverter under non-uniform insolation conditions by hardware-in-the-loop test

被引:19
作者
Iman-Eini, Hossein [1 ]
Tennakoon, Sarath B. [2 ]
机构
[1] Univ Tehran, Coll Engn, Sch Elect & Comp Engn, Tehran, Iran
[2] Staffordshire Univ, Sch Creat Arts & Engn, Stoke On Trent, Staffs, England
关键词
Cascaded H-bridge inverter; Grid connection; Hardware-in-the-loop implementation; Photovoltaics; Real-time simulation; SYSTEMS; MODULATION; CONVERTER;
D O I
10.1016/j.ijepes.2018.08.017
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In this paper, the cascaded H-bridge (CHB) multilevel inverter is employed as a grid connected inverter. This kind of inverter has interesting features compared to conventional inverters, including better efficiency, lower THD, lower common mode current injection, and better waveform quality. Using a series connection of H-bridge cells in this topology, a high modularity is achieved and a stepwise voltage waveform is synthesized at the ac side, leading to lower filter size and complexity. This topology processes the electric power in one stage and does not need any step-up voltage transformer for grid connection. The dynamic performance of control system is studied through simulations and is compared with the conventional approach. In addition, a new voltage estimation approach is proposed to reduce the number of voltage sensors compared to existing methods. The simulation results are presented for a 1.5 kW grid connected 7-level CHB inverter and then the hardware-in-the loop implementation of the CHB inverter is presented to verify the performance of control system.
引用
收藏
页码:330 / 340
页数:11
相关论文
共 23 条
[1]   Renewable energy systems with photovoltaic power generators: Operation and modeling [J].
Bialasiewicz, Jan T. .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2008, 55 (07) :2752-2758
[2]   A Multilevel Inverter for Photovoltaic Systems With Fuzzy Logic Control [J].
Cecati, Carlo ;
Ciancetta, Fabrizio ;
Siano, Pierluigi .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2010, 57 (12) :4115-4125
[3]  
Cha H, 2009, IEEE INT POWER ELEC, P2198
[4]  
Eskandari A., 2013, P 3 INT C EL POW EN, P1, DOI [10.1109/EPECS.2013.6713006, DOI 10.1109/EPECS.2013.6713006]
[5]  
Farivar G, IEEE T IND ELECT
[6]   Improved control algorithm for grid-connected cascaded H-bridge photovoltaic inverters under asymmetric operating conditions [J].
Iman-Eini, Hossein ;
Bacha, Seddik ;
Frey, David .
IET POWER ELECTRONICS, 2018, 11 (03) :407-415
[7]   A Multilevel Medium-Voltage Inverter for Step-Up-Transformer-Less Grid Connection of Photovoltaic Power Plants [J].
Islam, Md Rabiul ;
Guo, Youguang ;
Zhu, Jianguo .
IEEE JOURNAL OF PHOTOVOLTAICS, 2014, 4 (03) :881-889
[8]   A review of single-phase grid-connected inverters for photovoltaic modules [J].
Kjaer, SB ;
Pedersen, JK ;
Blaabjerg, F .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2005, 41 (05) :1292-1306
[9]   Control of a cascaded H-bridge multilevel converter for grid connection of photovoltaic systems [J].
Kouro, Samir ;
Wu, Bin ;
Moya, Alvaro ;
Villanueva, Elena ;
Correa, Pablo ;
Rodriguez, Jose .
IECON: 2009 35TH ANNUAL CONFERENCE OF IEEE INDUSTRIAL ELECTRONICS, VOLS 1-6, 2009, :3775-+
[10]   Grid-Connected Photovoltaic Systems: An Overview of Recent Research and Emerging PV Converter Technology [J].
Kouro, Samir ;
Leon, Jose I. ;
Vinnikov, Dmitri ;
Franquelo, Leopoldo G. .
IEEE INDUSTRIAL ELECTRONICS MAGAZINE, 2015, 9 (01) :47-61