DEVELOPMENT TESTING of ±800kV HVDC THYRISTOR VALVES

被引:0
作者
Ashraf, Muhammad
Gunatilake, Aruna
MacLeod, Norman
机构
来源
UPEC: 2009 44TH INTERNATIONAL UNIVERSITIES POWER ENGINEERING CONFERENCE | 2009年
关键词
BEM; Clearance; Corona shield; Electric Stress; HVDC; Prototype; SI Test; Thyristor Valve; UHVDC; 800; kV;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This paper describes the development work leading to the design and testing work of a new corona shield for AREVA's 800 kV Ultra High Voltage Direct Current (UHVDC) thyristor valve. The design of the corona shields required an extensive electrostatic field investigation using numerical analysis, particularly the Boundary Element Method (BEM), an enhancement of the well known Finite Element analysis to calculate electrical stress. Some results from the laboratory tests are presented in the paper together with an assessment of the initial BEM analysis. The paper concludes by considering how the electrical clearances identified in the tests influence the design, and hence achieve an economically viable corona shield design for +/-800 kV UHVDC convertor stations.
引用
收藏
页码:810 / 814
页数:5
相关论文
共 8 条
  • [1] ARRILLAGA J, 1988, HIGH VOLTAGE DIRECT, P86
  • [2] *CIGRE, 2002, 1432 CIGRE WG
  • [3] DAVIDSON CC, 2009, UHV POW TRANSM S BEI
  • [4] MACLEOD NM, 2009, 2 INT S STAND ULT VO
  • [5] MACLEOD NM, 2009, DEV RANGE PRODUCTS T
  • [6] MACLEOD NM, 2007, IEC CIGRE UHV S BEIJ
  • [7] RYAN HM, 2001, HIGH VOLTAGE ENG TES, P138
  • [8] STURGESS J, 2008, DEV INSULATION STRUC