Field measurements on indoor air quality of a residential building in Xi'an under different ventilation modes in winter

被引:27
|
作者
Sui, Xuemin [1 ]
Tian, Zhongjie [1 ]
Liu, Huitao [1 ]
Chen, Hao [1 ]
Wang, Dong [1 ]
机构
[1] Changan Univ, Sch Civil Engn, 75 Changan Middle Rd, Xian 710061, Peoples R China
来源
JOURNAL OF BUILDING ENGINEERING | 2021年 / 42卷
关键词
Residential building; Natural ventilation; Mechanical ventilation system; Ventilation rate; Indoor air quality; NATURAL VENTILATION; PM2.5; EXPOSURE; RATES; STRATEGIES; CHINA;
D O I
10.1016/j.jobe.2021.103040
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
In recent years, China is facing severe haze pollution in winter. More and more newly built residential buildings are installed with mechanical ventilation systems. In order to explore the system's application effect, this study selected a new typical residential building in Xi'an, China, and conducted a series of field measurements on indoor air quality (IAQ) under different ventilation modes. Several indoor pollutants including CO2, PM2.5, HCHO, TVOC, CO, and O-3 were monitored. Four ventilation modes were considered including natural infiltration, window-opening ventilation, and two mechanical ventilation modes with low and high ventilation rates. The ventilation rates and IAQ under different ventilation modes were evaluated and compared. In order to better analyze the causes of some measurement results, numerical simulation was also employed to simulate the air distribution. The results showed that the measured values of the air change per hour of the four ventilation modes were about 0.2 h(-1), 1.2 h(-1), 2.15 h(-1), 2.84 h(-1), respectively. The indoor concentrations of HCHO, TVOC, CO, and O-3 could all be controlled far below the Chinese limit under all ventilation modes. The indoor CO2 concentration under the natural infiltration mode reached 3300 ppm. The window-opening ventilation could only reduce the indoor CO2 concentrations for a short time, and the indoor PM2.5 concentrations were far above the Chinese limit in haze days. The mechanical ventilation system with filter could effectively avoid the influence of haze weather on indoor PM2.5 concentration. But the control effect of CO2 concentration was not satisfactory. The indoor CO2 concentrations under the two mechanical ventilation modes reached 1900 ppm and 1500 ppm, respectively. The simulation results indicated it was caused by the short circuit of airflow. It is suggested that significantly more attention should be paid to the design of air distribution of residential mechanical ventilation. This study is expected to contribute field data for natural and mechanical ventilation modes and also provides a guidance for the optimization of residential mechanical ventilation.
引用
收藏
页数:15
相关论文
共 50 条
  • [1] VENTILATION AND INDOOR AIR-QUALITY FIELD-MEASUREMENTS
    TURNER, WA
    HARLOS, DP
    SPENGLER, JD
    ASHRAE JOURNAL-AMERICAN SOCIETY OF HEATING REFRIGERATING AND AIR-CONDITIONING ENGINEERS, 1984, 26 (05): : 55 - 55
  • [2] Ventilation and Indoor Air Quality in Residential Bedrooms
    Fritz, Hagen
    Kinney, Kerry
    Schnyer, David
    Nagy, Zoltan
    ASHRAE TRANSACTIONS 2021, VOL 127, PT 2, 2021, 127 : 500 - 508
  • [3] DETERMINATION OF INDOOR AND OUTDOOR AIR QUALITY UNDER DIFFERENT VENTILATION CONDITIONS IN A RESIDENTIAL AREA OF LAHORE, PAKISTAN
    Abbas, M.
    Razzaq, S.
    Shahzadi, R.
    Rahman, A.
    Manzoor, F.
    Ali, Z.
    JOURNAL OF ANIMAL AND PLANT SCIENCES, 2015, 25 (03): : 672 - 676
  • [4] Analysis of Indoor Air Quality in Different Exhaust Conditions in Residential Buildings in Winter
    Wang, Yueren
    Wu, Nan
    Qi, Wei
    PROGRESS IN ENVIRONMENTAL SCIENCE AND ENGINEERING, PTS 1-4, 2013, 610-613 : 2823 - 2826
  • [5] BUILDING VENTILATION AND INDOOR AIR-QUALITY
    BERK, JV
    AMERICAN CERAMIC SOCIETY BULLETIN, 1980, 59 (03): : 327 - 327
  • [6] A New Perspective on Residential Building Ventilation from the Point of View of Achieving the Desired Indoor Air Quality using Different Ventilation Systems
    Strakova, Zuzana
    Markova, Julia
    SLOVAK JOURNAL OF CIVIL ENGINEERING, 2023, 31 (01) : 45 - 51
  • [7] Editorial - Ventilation and indoor air quality in residential dwellings
    Zhang, Tengfei
    Pei, Jingjing
    BUILDING AND ENVIRONMENT, 2019, 148 : 198 - 199
  • [8] Indoor air quality during sleep under different ventilation patterns
    Canha, Nuno
    Lage, Joana
    Candeias, Susana
    Alves, Celia
    Almeida, Susana Marta
    ATMOSPHERIC POLLUTION RESEARCH, 2017, 8 (06) : 1132 - 1142
  • [9] Wind tunnel measurements of indoor air quality in a building with natural cross-ventilation
    Diaz-Calderon, S. F.
    Gromke, C.
    Castillo, J. A.
    Huelsz, G.
    REVISTA MEXICANA DE FISICA, 2025, 71 (01)
  • [10] Analysis on influence of winter opening windows for natural ventilation on indoor fresh air volume in northern residential building
    Li, HuiXing
    Guan, Ying
    Feng, GuoHui
    Huang, Kailiang
    10TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATION AND AIR CONDITIONING, ISHVAC2017, 2017, 205 : 3323 - 3327