Influence of sand to coarse aggregate ratio on the interfacial bond strength of steel fibers in concrete for nuclear power plant

被引:54
作者
Kim, Jung Jin [1 ]
Kim, Dong Joo [1 ]
Kang, Su Tae [2 ]
Lee, Jang Hwa [3 ]
机构
[1] Sejong Univ, Dept Civil & Environm Engn, Seoul 143747, South Korea
[2] Daegu Univ, Dept Civil Engn, Gyongsan 712714, Gyeongbuk, South Korea
[3] Korea Inst Construct Technol, Goyang Si 411712, Gyeonggi Do, South Korea
关键词
MECHANICAL-PROPERTIES; IMPACT RESPONSE; IMAGE-ANALYSIS; BEHAVIOR; SIZE; ITZ;
D O I
10.1016/j.nucengdes.2012.07.004
中图分类号
TL [原子能技术]; O571 [原子核物理学];
学科分类号
0827 ; 082701 ;
摘要
The interfacial bond strength of three high strength steel fibers (smooth, hooked, and twisted fiber) in concrete of nuclear power plants was investigated to develop fiber reinforced concrete for containment building. Sand to aggregate ratio (S/a) was adjusted to compensate reduction in the workability due to adding fibers; the influence of S/a ratio on the interfacial bond strength was investigated. As the S/a ratio increased from 0.444 to 0.615, the bond strength of twisted steel fiber was significantly improved while smooth and hooked steel fiber showed no clear difference. The different sensitivity according to the S/a ratio results from the different pullout mechanism: twisted steel fiber generates more mechanical interaction during fiber pullout at the interface between fiber and matrix than smooth and hooked fibers. The microscopic observation by scanning electron microscope back-scattered electrons images discovered lower porosity at the interfacial transition zone between fiber and concrete with higher S/a ratio. (c) 2012 Elsevier B.V. All rights reserved.
引用
收藏
页码:1 / 10
页数:10
相关论文
共 38 条
[1]   Aircraft crash upon outer containment of nuclear power plant [J].
Abbas, H ;
Paul, DK ;
Godbole, PN ;
Nayak, GC .
NUCLEAR ENGINEERING AND DESIGN, 1996, 160 (1-2) :13-50
[2]  
Alwan JM., 1999, Concr. Sci. Eng, V1, P15
[3]  
American Society of Mechanical Engineers, 2011, COD CONCR CONT ASME, P5
[4]   FIBER-REINFORCED CEMENT-BASED COMPOSITES UNDER TENSILE IMPACT [J].
BANTHIA, N ;
CHOKRI, K ;
OHAMA, Y ;
MINDESS, S .
ADVANCED CEMENT BASED MATERIALS, 1994, 1 (03) :131-141
[5]   DEFORMED STEEL FIBER - CEMENTITIOUS MATRIX BOND UNDER IMPACT [J].
BANTHIA, N ;
TROTTIER, JF .
CEMENT AND CONCRETE RESEARCH, 1991, 21 (01) :158-168
[6]  
Banthia N, 1996, ACI MATER J, V93, P472
[7]   A review of the work of the RILEM TC 159-ETC: Engineering of the interfacial transition zone in cementitious composites [J].
Bentur, A ;
Alexander, MG .
MATERIALS AND STRUCTURES, 2000, 33 (226) :82-87
[8]  
Bindiganavile V, 2002, ACI MATER J, V99, P543
[9]   The ITZ in concrete - a different view based on image analysis and SEM observations [J].
Diamond, S ;
Huang, JD .
CEMENT & CONCRETE COMPOSITES, 2001, 23 (2-3) :179-188
[10]   Considerations in image analysis as applied to investigations of the ITZ in concrete [J].
Diamond, S .
CEMENT & CONCRETE COMPOSITES, 2001, 23 (2-3) :171-178