Motor winding problems - Caused by inverter drives

被引:40
作者
Fenger, M [1 ]
Campbell, SR
Pedersen, J
机构
[1] Iris Power Engn Inc, Toronto, ON, Canada
[2] Techwise AS, Fredericia, Denmark
关键词
D O I
10.1109/MIA.2003.1206913
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
An investigation into stator winding failures caused by the voltage surge environment is presented. Measurements of the surge voltage characteristics from a group of eight low-voltage motors driven by inverter-fed drives are discussed. Partial discharge activity in the motors was identified as the root cause of the deterioration and the eventual failure of the stator windings.
引用
收藏
页码:22 / 31
页数:10
相关论文
共 13 条
  • [1] BOEHNE EW, 1930, T AIEE, P1587
  • [2] PRACTICAL CALCULATION OF SWITCHING SURGES AT MOTOR TERMINALS
    DICK, EP
    GUPTA, BK
    PILLAI, P
    NARANG, A
    SHARMA, DK
    [J]. IEEE TRANSACTIONS ON ENERGY CONVERSION, 1988, 3 (04) : 864 - 872
  • [3] FENGER M, 2002 ANN REP C EL IN, P501
  • [4] FENGER M, 2001 ANN REP C EL IN, P352
  • [5] TURN INSULATION CAPABILITY OF LARGE AC MOTORS .1. SURGE MONITORING
    GUPTA, BK
    LLOYD, BA
    STONE, GC
    CAMPBELL, SR
    SHARMA, DK
    NILSSON, NE
    [J]. IEEE TRANSACTIONS ON ENERGY CONVERSION, 1987, 2 (04) : 658 - 665
  • [6] Lanier C, 1998, CONFERENCE RECORD OF THE 1998 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, VOLS 1 AND 2, P229, DOI 10.1109/ELINSL.1998.704706
  • [7] Lynn A. L., 1985, Proceedings of the 17th Electrical/Electronics Insulation Conference (Cat. No.85CH2133-7), P308
  • [8] TRANSIENT EFFECTS IN APPLICATION OF PWM INVERTERS TO INDUCTION-MOTORS
    PERSSON, E
    [J]. IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1992, 28 (05) : 1095 - 1101
  • [9] SAUNDERS LA, 1996, IEEE IAS PETR CHEM I, P75
  • [10] Inverter-fed drives: Which motor stators are at risk?
    Stone, G
    Campbell, S
    Tetreault, S
    [J]. IEEE INDUSTRY APPLICATIONS MAGAZINE, 2000, 6 (05) : 17 - 22