Mass flowrate characteristics of supercritical CO2 flowing through an electronic expansion valve

被引:20
作者
Hou, Yu [1 ,2 ]
Liu, Changhai [1 ]
Ma, Juanli [1 ]
Cao, Jing [1 ]
Chen, Shuangtao [1 ]
机构
[1] Xi An Jiao Tong Univ, State Key Lab Multiphase Flow Power Engn, Xian 710049, Peoples R China
[2] Xi An Jiao Tong Univ, Sch Energy & Power Engn, Xian 710049, Peoples R China
来源
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID | 2014年 / 47卷
关键词
Transcritical CO2 system; Supercritical CO2; EEV; Mass flowrate characteristics; Refrigeration; R410A; R22; PRESSURE; SYSTEM; R407C;
D O I
10.1016/j.ijrefrig.2014.04.008
中图分类号
O414.1 [热力学];
学科分类号
摘要
Electronic expansion valves (EEV) are employed increasingly in transcritical CO2 systems. In order to investigate the mass flowrate characteristics of supercritical CO2 flowing through an EEV, the effects of EEV outlet pressure on the mass flowrate of CO2 is studied under constant EEV inlet pressure and inlet temperature. The two-phase flow patterns of supercritical CO2 flowing through an EEV are revealed, and the conventional choked flow judgment formulas is proved effective for supercritical CO2. Based on Bernoulli Equation with expansion factor, the mass flowrate correlation of supercritical CO2 flowing through an EEV is presented. The influence of the expansion coefficient on the mass flowrate is considered in the correlation in which the correction coefficient is only affected by the EEV opening, the changing rate of the density and the pressure difference in the entrance region. The mass flowrate predicted by the correlation in this paper shows a good agreement with experimental data. The maximum relative errors are within 10%. The average and standard deviations are 0.76% and 5.9%, respectively. (C) 2014 Elsevier Ltd and IIR. All rights reserved.
引用
收藏
页码:134 / 140
页数:7
相关论文
共 22 条
  • [1] American National Standard, 2002, 6053421 IEC AM NAT S
  • [2] Bruderer H., 2008, 9 INT IEA HEAT PUMP, P20
  • [3] Experimental evaluation of the energy efficiency of a CO2 refrigerating plant working in transcritical conditions
    Cabello, R.
    Sanchez, D.
    Llopis, R.
    Torrella, E.
    [J]. APPLIED THERMAL ENGINEERING, 2008, 28 (13) : 1596 - 1604
  • [4] Experimental investigation on mass flow characteristics of electronic expansion valves with R22, R410A and R407C
    Chen Liang
    Chen Jiangping
    Liu Jinghui
    Chen Zhijiu
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2009, 50 (04) : 1033 - 1039
  • [5] Capacity modulation of an inverter-driven multi-air conditioner using electronic expansion valves
    Choi, JM
    Kim, YC
    [J]. ENERGY, 2003, 28 (02) : 141 - 155
  • [6] Davies A., 1973, ASHRAE T 1, V79, P109
  • [7] Simplified modeling analysis of mass flow characteristics in electronic expansion valve
    Li, Wenhua
    [J]. APPLIED THERMAL ENGINEERING, 2013, 53 (01) : 8 - 12
  • [8] Choking phenomenon and pressure drop mechanism in electronic expansion valves
    Liu, Jinghui
    Chen, Jiangping
    Chen, Zhijiu
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2008, 49 (06) : 1321 - 1330
  • [9] A new model for depicting mass flow rate characteristic of electronic expansion valves
    Liu, Jinghui
    Chen, Jiangping
    Ye, Qifang
    Chen, Zhijiu
    [J]. EXPERIMENTAL THERMAL AND FLUID SCIENCE, 2007, 32 (01) : 214 - 219
  • [10] Experimentation and correlation of R744 two-phase flow through short tubes
    Liu, JP
    Niu, YM
    Chen, JP
    Chen, ZJ
    Feng, X
    [J]. EXPERIMENTAL THERMAL AND FLUID SCIENCE, 2004, 28 (06) : 565 - 573