Development of Fault Detector for Series Arc Fault in Low Voltage DC Distribution System using Wavelet Singular Value Decomposition and State Diagram

被引:11
作者
Oh, Yun-Sik [1 ]
Han, Joon [1 ]
Gwon, Gi-Hyeon [1 ]
Kim, Doo-Ung [1 ]
Kim, Chul-Hwan [1 ]
机构
[1] Sungkyunkwan Univ, Coll Informat & Commun Engn, Seoul, South Korea
关键词
EMTP; Fault Detector; LVDC; Series Arc Fault; State Diagram; WSVD; POWER-SYSTEMS;
D O I
10.5370/JEET.2015.10.3.766
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
It is well known that series arc faults in Low Voltage DC (LVDC) distribution system occur at unintended points of discontinuity within an electrical circuit. These faults can make circuit breakers not respond timely due to low fault current. It, therefore, is needed to detect the series fault for protecting circuits from electrical fires. This paper proposes a novel scheme to detect the series arc fault using Wavelet Singular Value Decomposition (WSVD) and state diagram. In this paper, the fault detector developed is designed by using three criterion factors based on the RMS value of Singular value of Approximation (SA), Sum of the absolute value of Detail (SD), and state diagram. LVDC distribution system including AC/DC and DC/DC converter is modeled to verify the proposed scheme using ElectroMagnetic Transient Program (EMTP) software. EMTP/MODELS is also utilized to implement the series arc model and WSVD. Simulation results according to various conditions clearly show the effectiveness of the proposed scheme.
引用
收藏
页码:766 / 776
页数:11
相关论文
共 28 条
  • [1] Agustoni, 2005, P INT C EL DISTR CIR
  • [2] [Anonymous], P NORPIE 2008 C
  • [3] Overcurrent protection on voltage-source-converter-based multiterminal DC distribution systems
    Baran, Mesut E.
    Mahajan, Nikhil R.
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2007, 22 (01) : 406 - 412
  • [4] High power quality and DG integrated low voltage dc distribution system
    Brenna, M.
    Lazaroiu, G. C.
    Tironi, E.
    [J]. 2006 POWER ENGINEERING SOCIETY GENERAL MEETING, VOLS 1-9, 2006, : 3384 - +
  • [5] Georgakis D, 2004, IEEE POWER ELECTRON, P2521
  • [6] Guo Yunmei, 2009, 2009 4th IEEE Conference on Industrial Electronics and Applications, P4013, DOI 10.1109/ICIEA.2009.5138962
  • [7] He ZY, 2004, PROCEEDINGS OF THE 2004 INTERNATIONAL CONFERENCE ON INTELLIGENT MECHATRONICS AND AUTOMATION, P433
  • [8] UNIQUE ASPECTS OF DISTRIBUTION-SYSTEM HARMONICS DUE TO HIGH IMPEDANCE GROUND FAULTS
    JEERINGS, DI
    LINDERS, JR
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 1990, 5 (02) : 1086 - 1094
  • [9] Simulation of the gasdynamic and electromagnetic processes in low voltage switching arcs
    Karetta, F
    Lindmayer, M
    [J]. IEEE TRANSACTIONS ON COMPONENTS PACKAGING AND MANUFACTURING TECHNOLOGY PART A, 1998, 21 (01): : 96 - 103
  • [10] A novel fault-detection technique of high-impedance arcing faults in transmission lines using the wavelet transform
    Kim, CH
    Kim, H
    Ko, YH
    Byun, SH
    Aggarwal, RK
    Johns, AT
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2002, 17 (04) : 921 - 929