Comparisons among VOCs measured in three types of US commercial buildings with different occupant densities

被引:91
作者
Shields, HC
Fleischer, DM
Weschler, CJ
机构
[1] Bellcore, Red Bank, NJ 07701
来源
INDOOR AIR-INTERNATIONAL JOURNAL OF INDOOR AIR QUALITY AND CLIMATE | 1996年 / 6卷 / 01期
关键词
volatile organic compounds; indoor/outdoor; ventilation; source control; occupant density;
D O I
10.1111/j.1600-0668.1996.t01-3-00002.x
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Volatile organic compounds (VOCs) have been simultaneously measured indoors and outdoors at 50 sparsely occupied telecommunications (Telco) offices, 9 variably occupied data centers and 11 densely occupied administrative (Admin) offices. Comparisons among the three building types, as well as within each of the building types, showed the influence of ventilation and sources. On average, the Telco and Admin facilities were better ventilated than the Data Centers, and the geometric mean of the I/O's for Sigma VOC (sum of the concentrations of identified VOCs) at Telco (3.2) and Admin (5.3) facilities were lower than at Data Centers (8.6). Admin Offices had more and stronger sources than Telco Offices; when comparably ventilated facilities were compared, many VOCs had I/O ratios that were significantly larger at the Admin Offices. Furthermore, certain VOCs were detected in Admin but not Telco Offices. The influence of human occupancy on indoor VOCs was gauged by comparing sparsely and densely occupied buildings. Octamethylcyclotetrasiloxane (D4), decamethylcyclopentasiloxane (D5), n-dodecane (n-C12) through n-hexadecane (n-C16), limonene, and, to a lesser extent, tetrachloroethylene were all present in higher concentrations when there were more occupants (per unit area). Within this set of compounds, D5 was the best marker of occupant density.
引用
收藏
页码:2 / 17
页数:16
相关论文
共 27 条
  • [1] [Anonymous], 1993, Journal of Indoor Air, DOI DOI 10.1111/J.1600-0668.1993.T01-1-00002.X
  • [2] BELLCORE, 1991, VENTILATION CENTRAL
  • [3] CONCENTRATIONS OF VOLATILE ORGANIC-COMPOUNDS IN INDOOR AIR - A REVIEW
    BROWN, SK
    SIM, MR
    ABRAMSON, MJ
    GRAY, CN
    [J]. INDOOR AIR-INTERNATIONAL JOURNAL OF INDOOR AIR QUALITY AND CLIMATE, 1994, 4 (02): : 123 - 134
  • [4] CLAUSEN PA, 1991, INDOOR AIR, V1, P562
  • [5] DAISEY JM, 1994, ATMOS ENVIRON, V22, P3557
  • [6] DEBORTOLI M, 1986, 10487 EUR EN COMM EU
  • [7] DEBORTOLI M, 1984, 9450 EUR EN COMM EUR
  • [8] Gosselin R.E., 1984, Clinical Toxicology of Commercial Products
  • [9] GUSTAFSSON H, 1992, BUILDING MAT IDENTIF
  • [10] SOURCES AND SOURCE STRENGTHS OF VOLATILE ORGANIC-COMPOUNDS IN A NEW OFFICE BUILDING
    HODGSON, AT
    DAISEY, JM
    GROT, RA
    [J]. JOURNAL OF THE AIR & WASTE MANAGEMENT ASSOCIATION, 1991, 41 (11): : 1461 - 1468