Comparison of Dissolved Gas Interpretation Techniques in Mineral Oil Immersed Transformers

被引:0
|
作者
Balivada, Santhosh Kumar [1 ]
Karmakar, Subrata [1 ]
机构
[1] Natl Inst Technol Rourkela, Dept Elect Engn, Rourkela, Odisha, India
来源
2022 IEEE 6TH INTERNATIONAL CONFERENCE ON CONDITION ASSESSMENT TECHNIQUES IN ELECTRICAL SYSTEMS, CATCON | 2022年
关键词
Power transformer; Dissolved gas analysis; Incipient fault; FAULTS;
D O I
10.1109/CATCON56237.2022.10077623
中图分类号
TP3 [计算技术、计算机技术];
学科分类号
0812 ;
摘要
One of the most important techniques for recognizing the potential fault in a power transformer at an early stage, i.e., incipient state, can be done through the interpretation of Dissolved Gas Analysis (DGA). Depending on the nature and seriousness of the fault, the insulation breakdown starts instantaneously, and the decomposition products will be distinct. DGA is periodically used to test the transformer's insulation oil to obtain dissolved gases that developed as an outcome of degradation in interior insulating materials. A conclusion can be drawn from the data obtained by DGA using distinct interpretation techniques. However, for the same instance, they could diagnose different fault categories. The purpose of this research is to examine the performance of different DGA interpretation techniques, i.e., Doernenburg Ratio Method (DRM), Rogers Ratio Method (RRM), IEC Ratio Method (IRM), Duval Triangle Method (DTM) and Duval Pentagon Method (DPM), [1] and evaluate these methods from fifty predetermined fault cases obtained from the IEEE Dataport in Enwen Li datasheet [2] using python. This study not only compares these techniques' overall accuracy but also focuses on the effectiveness of each method's ability to identify a particular fault separately.
引用
收藏
页码:403 / 407
页数:5
相关论文
共 50 条
  • [1] Implementation of a Condition Monitoring Software for Mineral Oil-Immersed Transformers via Dissolved Gas In-Oil Analysis
    Torres, Jorge
    Guerrero, Jose M.
    Leones, Wilson
    Platero, Carlos A.
    2021 21ST IEEE INTERNATIONAL CONFERENCE ON ENVIRONMENT AND ELECTRICAL ENGINEERING AND 2021 5TH IEEE INDUSTRIAL AND COMMERCIAL POWER SYSTEMS EUROPE (EEEIC/I&CPS EUROPE), 2021,
  • [2] Proposed three ratios technique for the interpretation of mineral oil transformers based dissolved gas analysis
    Gouda, Osama E.
    El-Hoshy, Salah H.
    L-Tamaly, Hassan H. E.
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2018, 12 (11) : 2650 - 2661
  • [3] Predictive Modelingof Dissolved Gas Concentrationin Oil-Immersed Substation Transformers
    Kim, Younghun
    Goyal, Aanchal
    Kumar, Tarun
    2016 THE 4TH IEEE INTERNATIONAL CONFERENCE ON SMART ENERGY GRID ENGINEERING (SEGE), 2016, : 261 - 267
  • [4] Probabilistic Modeling of Dissolved Gas Concentration for Predicting Operating Status of Oil-Immersed Transformers
    Shao, Jianwei
    Wang, Junhua
    Pan, Xiao
    Wang, Ruilin
    Liu, Shuxun
    Jin, Zhanxiang
    Wang, Ziqing
    IEEE TRANSACTIONS ON INDUSTRIAL INFORMATICS, 2025, 21 (02) : 1339 - 1348
  • [5] Classification Method in Fault Diagnosis of Oil-Immersed Power Transformers by Considering Dissolved Gas Analysis
    Rosmaliati
    Aji, Bernandus Anggo Seno
    Hafidz, Isa
    Priyadi, Ardyono
    Purnomo, Mauridhi Hery
    EMITTER-INTERNATIONAL JOURNAL OF ENGINEERING TECHNOLOGY, 2022, 10 (02) : 233 - 245
  • [6] SURVEY ON THE ANALYSIS OF GAS-FORMATION IN OIL IMMERSED TRANSFORMERS
    FOSCHUM, H
    ELIN ZEITSCHRIFT, 1980, 32 (1-2): : 17 - 26
  • [7] Effects of Metal Passivator Degradation on the Dissolved Gases Characteristics of Oil in Oil-immersed Transformers
    Gao, Si-hang
    Zeng, Xi-Song
    Zhang, Guo-wen
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2021, 28 (05) : 1735 - 1742
  • [8] Development of Dissolved Gas Analysis(DGA) Expert System Using New Diagnostic Algorithm For Oil-immersed Transformers
    Kim, Y. M.
    Lee, S. J.
    Seo, H. D.
    Jung, J. R.
    Yang, H. J.
    PROCEEDINGS OF 2012 IEEE INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS (IEEE CMD 2012), 2012, : 365 - 368
  • [9] Retrofilling Mineral Oil-Immersed Transformers with Alternative Insulating Liquids: A Review
    Montero, Andres
    Garcia, Belen
    IEEE ELECTRICAL INSULATION MAGAZINE, 2024, 40 (06) : 6 - 22
  • [10] Novel Probabilistic Neural Network Models Combined with Dissolved Gas Analysis for Fault Diagnosis of Oil-Immersed Power Transformers
    Zhou, Yichen
    Tao, Lingyu
    Yang, Xiaohui
    Yang, Li
    ACS OMEGA, 2021, 6 (28): : 18084 - 18098