Hybrid renewable power plant sizing - Graphical decision tool, sensitivity analysis and applications in Ajaccio and Tilos

被引:6
作者
Duchaud, Jean-Laurent [1 ]
Notton, Gilles [1 ]
Fouilloy, Alexis [1 ]
Voyant, Cyril [2 ]
机构
[1] Univ Corsica, Res Ctr Georges Peri, UMR CNRS 6134, Corte, Corsica, France
[2] Univ La Reunion, PIMENT Lab, EA 4518, St Denis, Reunion, France
基金
欧盟地平线“2020”;
关键词
Hybrid power plant; Optimal sizing; Techno-economic study; Sensitivity analysis; Energy Management Strategies; RAMP-RATE CONTROL; ENERGY-STORAGE; BATTERY; SOLAR; SYSTEM; OPTIMIZATION; WIND; DESIGN; SIZE;
D O I
10.1016/j.apenergy.2019.113601
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
When sizing a renewable energy power plant in a grid-connected scenario, the optimal solution depends on the energy exchange rates between the actors of the electrical network. This study presents an optimization method that can be adapted to various power plant configurations to obtain the best size for each component, depending on the weather and the consumption. The optimization problem is solved in two steps. A Multi-Objective Particle Swarm Optimizer gives the trade-off between the cost of the components and the amount of non-renewable energy used, then the posttreatment takes into account the energy exchange tariffs and presents the solutions that minimize the production cost for any import and export rates. Those results can be used to evaluate the feasibility of an installation or to define the exchange tariffs with the grid regulation entity. This study also showcases the effect of the economic assumptions and of the choice of the energy management strategy on the optimal solution. The results show that the variation of the optimal production cost is limited but the component size has to be adapted accordingly. In the same way, the Energy Management Strategy used influences the plant design without affecting significantly the production cost.
引用
收藏
页数:9
相关论文
共 48 条
  • [31] Using electrical energy storage in residential buildings - Sizing of battery and photovoltaic panels based on electricity cost optimization
    Koskela, Juha
    Rautiainen, Antti
    Jarventausta, Pertti
    [J]. APPLIED ENERGY, 2019, 239 : 1175 - 1189
  • [32] Pumped storage-based standalone photovoltaic power generation system: Modeling and techno-economic optimization
    Ma, Tao
    Yang, Hongxing
    Lu, Lin
    Peng, Jinqing
    [J]. APPLIED ENERGY, 2015, 137 : 649 - 659
  • [33] Integrated sizing and scheduling of wind/PV/diesel/battery isolated systems
    Malheiro, Andre
    Castro, Pedro M.
    Lima, Ricardo M.
    Estanqueiro, Ana
    [J]. RENEWABLE ENERGY, 2015, 83 : 646 - 657
  • [34] The electrical energy situation of French islands and focus on the Corsican situation
    Notton, G.
    Duchaud, J. L.
    Nivet, M. L.
    Voyant, C.
    Chalvatzis, K.
    Fouilloy, A.
    [J]. RENEWABLE ENERGY, 2019, 135 : 1157 - 1165
  • [35] Notton G, 2017, 2017 15TH INTERNATIONAL CONFERENCE ON ELECTRICAL MACHINES, DRIVES AND POWER SYSTEMS (ELMA), P102, DOI 10.1109/ELMA.2017.7955410
  • [36] Oguz Y, 2015, J ENERGY SOUTH AFR, V26, P70
  • [37] On recent advances in PV output power forecast
    Raza, Muhammad Qamar
    Nadarajah, Mithulananthan
    Ekanayake, Chandima
    [J]. SOLAR ENERGY, 2016, 136 : 125 - 144
  • [38] Reyes-Sierra M, 2006, Int. J. Comput. Intell. Res., V2, P287, DOI DOI 10.5019/J.IJCIR.2006.68
  • [39] Review of software tools for hybrid renewable energy systems
    Sinha, Sunanda
    Chandel, S. S.
    [J]. RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2014, 32 : 192 - 205
  • [40] Machine learning methods for solar radiation forecasting: A review
    Voyant, Cyril
    Notton, Gilles
    Kalogirou, Soteris
    Nivet, Marie-Laure
    Paoli, Christophe
    Motte, Fabrice
    Fouilloy, Alexis
    [J]. RENEWABLE ENERGY, 2017, 105 : 569 - 582