Statistical analysis of parameters influencing the relationship between outdoor and indoor air quality in schools

被引:105
作者
Poupard, O [1 ]
Blondeau, P [1 ]
Iordache, V [1 ]
Allard, F [1 ]
机构
[1] Univ La Rochelle, LEPTAB, F-17042 La Rochelle, France
关键词
schools; principal component analysis; I/O ratios; particulate matter; nitrogen dioxide; nitric oxide; ozone; building permeability;
D O I
10.1016/j.atmosenv.2004.12.016
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
Under the French national research program PRIMEQUAL, measurements of outdoor and indoor pollution have been performed in eight school buildings in La Rochelle (France) and its suburbs. The school buildings were either naturally ventilated by opening the windows or mechanically ventilated with minimum fresh air, and demonstrated various permeabilities. Ozone, nitrogen oxides (NO and NO2), and particulate matter (PM) (15 size intervals ranging from 0.3 to 20 mu m) concentrations were monitored continuously indoors and outdoors for two 2-week periods. The indoor relative humidity, temperature, CO2 concentration (room occupancy), window openings and permeability of the building were also measured. Principal component analysis (PCA), a multivariate observation-based statistical method, was used to determine the parameters influencing the relationship between the outdoor and indoor concentration levels. After a brief description of the experimental data and methodology, the paper presents a detailed analysis of the PCA diagrams. This analysis leads to distinguish between positively correlated, negatively correlated and non-correlated variables. The main conclusions arising from the study are: (1) the influence of the room occupancy on the particle concentrations indoors changes with different particle sizes, (2) the building air-tightness and the outdoor concentration level greatly influence the indoor/outdoor (I/O) concentration ratios of ozone, and (3) indoor ozone and particles concentrations are negatively correlated, which may be the result of complex homogeneous and/or heterogeneous processes. (c) 2005 Elsevier Ltd. All rights reserved.
引用
收藏
页码:2071 / 2080
页数:10
相关论文
共 10 条
[1]   Relationship between outdoor and indoor air quality in eight French schools [J].
Blondeau, P ;
Iordache, V ;
Poupard, O ;
Genin, D ;
Allard, F .
INDOOR AIR, 2005, 15 (01) :2-12
[2]  
BLONDEAU P, 2002, ETUDE IMPACT POLLUT
[3]   Comparison between indoor and outdoor air contaminant levels in residential buildings from passive sampler study [J].
Chao, CYH .
BUILDING AND ENVIRONMENT, 2001, 36 (09) :999-1007
[4]  
Jackson JE, 1991, A user's guide to principal component analysis
[5]  
Jolliffe I. T., 1986, Principal Component Analysis, DOI [DOI 10.1016/0169-7439(87)80084-9, 10.1007/0-387-22440-8_13, DOI 10.1007/0-387-22440-8_13]
[6]   Gas/particle partitioning of semivolatile organic compounds to model inorganic, organic, and ambient smog aerosols [J].
Liang, CK ;
Pankow, JF ;
Odum, JR ;
Seinfeld, JH .
ENVIRONMENTAL SCIENCE & TECHNOLOGY, 1997, 31 (11) :3086-3092
[7]   RELATIONSHIPS BETWEEN INDOOR AND OUTDOOR AIR-QUALITY IN 4 NATURALLY VENTILATED OFFICES IN THE UNITED-KINGDOM [J].
PHILLIPS, JL ;
FIELD, R ;
GOLDSTONE, M ;
REYNOLDS, GL ;
LESTER, JN ;
PERRY, R .
ATMOSPHERIC ENVIRONMENT PART A-GENERAL TOPICS, 1993, 27 (11) :1743-1753
[8]   The significance of secondary organic aerosol formation and growth in buildings: experimental and computational evidence [J].
Sarwar, G ;
Corsi, R ;
Allen, D ;
Weschler, C .
ATMOSPHERIC ENVIRONMENT, 2003, 37 (9-10) :1365-1381
[9]   The influence of ventilation on reactions among indoor pollutants: Modeling and experimental observations [J].
Weschler, CJ ;
Shields, HC .
INDOOR AIR, 2000, 10 (02) :92-100
[10]   Experiments probing the influence of air exchange rates on secondary organic aerosols derived from indoor chemistry [J].
Weschler, CJ ;
Shields, HC .
ATMOSPHERIC ENVIRONMENT, 2003, 37 (39-40) :5621-5631