Compensation of Voltage Sags and Swells Using Dynamic Voltage Restorer Based on Bi-Directional H-Bridge AC/AC Converter

被引:3
作者
Chen, Yu-Kai [1 ]
Qiu, Xian-Zhi [2 ]
Wu, Yung-Chun [1 ]
Song, Chau-Chung [1 ]
机构
[1] Natl Formosa Univ, Dept Aeronaut Engn, Huwei 632, Taiwan
[2] Fego Precis Ind Co Ltd, Taichung 413, Taiwan
关键词
DVR; H-bridge; voltage sag; voltage swell;
D O I
10.3390/pr9091541
中图分类号
TQ [化学工业];
学科分类号
0817 ;
摘要
In this paper, the compensation of voltage sags and swells using a dynamic voltage restorer (DVR) based on a bi-directional AC/AC converter is presented for stabilizing single-phase AC line voltage. The H-bridge AC/AC converter with bi-directional switches and without bulk capacitor is adopted as the power topology of the proposed system. The proposed novel topology of DVR is adopted to compensate both voltage sag and swell conditions. Additionally, the power factor is closed to unity because a bulk capacitor is not required. The inner and outer loop control is proposed to improve the response with gain scaling; gain control is adopted to reduce the overshoot. Finally, a 2 kVA prototype has been implemented to verify the performance and accuracy of the control method for the DVR system. The peak efficiency of the system is up to 94%, and it can compensate 50% voltage swells and 25% voltage sags.
引用
收藏
页数:14
相关论文
共 17 条
  • [1] [Anonymous], 2009, INT J COMPUT ELECT E, DOI DOI 10.7763/IJCEE.2009.V1.68
  • [2] Arrillaga J., 2000, Power System Quality Assessment
  • [3] Bhalerao S.N, 2017, INT J ADV RES ELECT, V6, P6501
  • [4] Bollen M.H., 1999, UNDERSTANDING POWER
  • [5] Boone P., 2006, INTERNAL ALCATEL LUC, P1
  • [6] Dynamic sag correctors: Cost-effective industrial power line conditioning
    Brumsickle, WE
    Schneider, RS
    Luckjiff, GA
    Divan, DM
    McGranaghan, MF
    [J]. IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2001, 37 (01) : 212 - 217
  • [7] Chunming Tu, 2019, CPSS Transactions on Power Electronics and Applications, V4, P219, DOI 10.24295/CPSSTPEA.2019.00021
  • [8] Hossein S.H., 2009, P 2009 INT C EL EL E, P1611
  • [9] Optimum Control Scheme of Output Voltage Based on Cascaded H-bridge DVR
    Jiang, Fei
    Cheng, Siju
    Tu, Chunming
    Guo, Qi
    Li, Qing
    Chen, Cheng
    [J]. CSEE JOURNAL OF POWER AND ENERGY SYSTEMS, 2020, 6 (02): : 249 - 258
  • [10] Control and testing of a dynamic voltage restorer (DVR) at medium voltage level
    Nielsen, JG
    Newman, M
    Nielsen, H
    Blaabjerg, F
    [J]. IEEE TRANSACTIONS ON POWER ELECTRONICS, 2004, 19 (03) : 806 - 813