Optimum distribution network operation considering distributed generation mode of operations and safety margin

被引:11
作者
Ing, Koong Gia [1 ]
Jamian, Jasrul Jamani [2 ]
Mokhlis, Hazlie [1 ,3 ]
Illias, Hazlee Azil [1 ,3 ]
机构
[1] Univ Malaya, Dept Elect Engn, Fac Engn, Kuala Lumpur 50603, Malaysia
[2] Univ Teknol Malaysia, Fac Elect Engn, Johor Baharu 81310, Johor, Malaysia
[3] Univ Malaya, UMPEDAC, Wisma R&D UM, Level 4, Kuala Lumpur 59990, Malaysia
关键词
distribution networks; distributed power generation; on load tap changers; distribution network; distributed generation mode; network reconfiguration; tap changer setting; optimal configuration process; power loss; imperialist competitive algorithm; photovoltaic generation; daily irradiance; daily load profile; IEEE; 33; system; five tie-switches; on-load tap changer; DISTRIBUTION-SYSTEMS; RECONFIGURATION; OPTIMIZATION;
D O I
10.1049/iet-rpg.2015.0533
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
This study analyse the impact of different distributed generation (DG) operating modes towards the system performance when network reconfiguration, DG generation and tap changer setting are simultaneously configure to optimal value. The main consideration in the optimal configuration process is to minimise daily power losses. For the purpose of optimisation, imperialist competitive algorithm is applied. Analysis is conducted based on safety margin of total DGs penetration, photovoltaic generation based on daily irradiance and daily load profile. The analysis of different DG mode of operations is conducted using IEEE 33 having five tie-switches and one on-load tap changer.
引用
收藏
页码:1049 / 1058
页数:10
相关论文
共 17 条
[1]  
Atashpaz-Gargari E, 2007, IEEE C EVOL COMPUTAT, P4661, DOI 10.1109/cec.2007.4425083
[2]   Optimal Renewable Resources Mix for Distribution System Energy Loss Minimization [J].
Atwa, Y. M. ;
El-Saadany, E. F. ;
Salama, M. M. A. ;
Seethapathy, R. .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2010, 25 (01) :360-370
[3]   Multiobjective daily Volt/VAr control in distribution systems with distributed generation using binary ant colony optimization [J].
Azimi, Reza ;
Esmaeili, Saeid .
TURKISH JOURNAL OF ELECTRICAL ENGINEERING AND COMPUTER SCIENCES, 2013, 21 (03) :613-629
[4]   NETWORK RECONFIGURATION IN DISTRIBUTION-SYSTEMS FOR LOSS REDUCTION AND LOAD BALANCING [J].
BARAN, ME ;
WU, FF .
IEEE TRANSACTIONS ON POWER DELIVERY, 1989, 4 (02) :1401-1407
[5]  
Dahaian Wardiah Mohd, 2013, Przeglad Elektrotechniczny, V89, P137
[6]   Feasibility analysis of stand-alone renewable energy supply options for a large hotel [J].
Dalton, G. J. ;
Lockington, D. A. ;
Baldock, T. E. .
RENEWABLE ENERGY, 2008, 33 (07) :1475-1490
[7]   Design and techno-economical optimization for hybrid PV/wind system under various meteorological conditions [J].
Diaf, S. ;
Notton, G. ;
Belhamel, M. ;
Haddadi, M. ;
Louche, A. .
APPLIED ENERGY, 2008, 85 (10) :968-987
[8]   Smart Grid - The New and Improved Power Grid: A Survey [J].
Fang, Xi ;
Misra, Satyajayant ;
Xue, Guoliang ;
Yang, Dejun .
IEEE COMMUNICATIONS SURVEYS AND TUTORIALS, 2012, 14 (04) :944-980
[9]  
Ing K. G., 2015, J APPL MATH, V501
[10]  
Lalitha M. Padma, 2010, Journal of Theoretical and Applied Information Technology, V13, P107