Coupling to control cables in HV substations

被引:3
作者
Lodwig, SG [1 ]
Schuetz, CC [1 ]
机构
[1] Exelon Corp, ComEd Substn Engn Serv, Willowbrook, IL USA
来源
2001 IEEE EMC INTERNATIONAL SYMPOSIUM, VOLS 1 AND 2 | 2001年
关键词
D O I
10.1109/ISEMC.2001.950621
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
PLC's and microprocessor relays located in control buildings inside the HV substations were subject to electrical interference substation yard during high voltage air disconnect switching. The interference was due to modifications to a circuit breaker that produced common mode voltages on control circuit wiring in the substation control building and led to equipment damage and misoperation. This paper describes the unusual coupling mechanism that created transient voltages, a comparison to between predicted and measured transients, and a description of use of shielded cable to minimize interference coupling.