Design Evaluation for a Finned-Tube CO2 Gas Cooler in Residential Applications

被引:3
作者
Alexopoulos, Charalampos [1 ]
Aljolani, Osama [2 ]
Heberle, Florian [2 ]
Roumpedakis, Tryfon C. [1 ]
Brueggemann, Dieter [2 ]
Karellas, Sotirios [1 ]
机构
[1] Natl Tech Univ Athens, Sch Mech Engn, Dept Thermal Engn, Lab Steam Boilers & Thermal Plants, 9 Heroon Polytech St, Zografos 15780, Greece
[2] Univ Bayreuth, Chair Engn Thermodynam & Transport Proc LTTT, Ctr Energy Technol ZET, Fac Engn Sci, Univ Str 30, Bayreuth, Germany
关键词
supercritical carbon dioxide; experimental testing; finned-tube gas cooler; HEAT-TRANSFER; CARBON-DIOXIDE; PRESSURE-DROP; SYSTEM; SIMULATION;
D O I
10.3390/en13102428
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Towards the introduction of environmentally friendlier refrigerants, CO2 cycles have gained significant attention in cooling and air conditioning systems in recent years. In this context, a design procedure for an air finned-tube CO2 gas cooler is developed. The analysis aims to evaluate the gas cooler design incorporated into a CO2 air conditioning system for residential applications. Therefore, a simulation model of the gas cooler is developed and validated experimentally by comparing its overall heat transfer coefficient. Based on the model, the evaluation of different numbers of rows, lengths, and diameters of tubes, as well as different ambient temperatures, are conducted, identifying the most suitable design in terms of pressure losses and required heat exchange area for selected operational conditions. The comparison between the model and the experimental results showed a satisfactory convergence for fan frequencies from 50 to 80 Hz. The absolute average deviations of the overall heat transfer coefficient for fan frequencies from 60 to 80 Hz were approximately 10%. With respect to the gas cooler design, a compromise between the bundle area and the refrigerant pressure drop was necessary, resulting in a 2.11 m(2) bundle area and 0.23 bar refrigerant pressure drop. In addition, the analysis of the gas cooler's performance in different ambient temperatures showed that the defined heat exchanger operates properly, compared to other potential gas cooler designs.
引用
收藏
页数:17
相关论文
共 28 条
[1]  
[Anonymous], 2019, MATLAB STAT TOOLB RE
[2]  
[Anonymous], 2015, CAL AIR RES BOARD DR
[3]  
Braimakis K., 2017, ADV NEW HEAT TRANSFE, P377
[4]   Modelling and Evaluation of the Thermohydraulic Performance of Finned-Tube Supercritical Carbon Dioxide Gas Coolers [J].
Chai, Lei ;
Tsamos, Konstantinos M. ;
Tassou, Savvas A. .
ENERGIES, 2020, 13 (05)
[5]   Analysis of supercritical CO2 cooling in macro- and micro-channels [J].
Cheng, Lixin ;
Ribatski, Gherhardt ;
Thome, John R. .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2008, 31 (08) :1301-1316
[6]   Heat Roadmap Europe: Large-Scale Electric Heat Pumps in District Heating Systems [J].
David, Andrei ;
Mathiesen, Brian Vad ;
Averfalk, Helge ;
Werner, Sven ;
Lund, Henrik .
ENERGIES, 2017, 10 (04)
[7]  
Dittus FW., 1985, Int Commun Heat Mass Transfer, V12, P3, DOI [10.1016/0735-1933(85)90003-X, DOI 10.1016/0735-1933(85)90003-X]
[8]   The Contribution of Non-CO2 Greenhouse Gas Mitigation to Achieving Long-Term Temperature Goals [J].
Gambhir, Ajay ;
Napp, Tamaryn ;
Hawkes, Adam ;
Hoeglund-Isaksson, Lena ;
Winiwarter, Wilfried ;
Purohit, Pallav ;
Wagner, Fabian ;
Bernie, Dan ;
Lowe, Jason .
ENERGIES, 2017, 10 (05)
[9]   Simulation and performance evaluation of finned-tube CO2 gas coolers for refrigeration systems [J].
Ge, Y. T. ;
Cropper, R. T. .
APPLIED THERMAL ENGINEERING, 2009, 29 (5-6) :957-965
[10]  
General Office of the State Council, 2014, CHIN STAT COUNC 2014