Wind in Weak Grids: Low-Frequency Oscillations, Subsynchronous Oscillations, and Torsional Interactions

被引:192
作者
Li, Yin [1 ]
Fan, Lingling [1 ]
Miao, Zhixin [1 ]
机构
[1] Univ S Florida, Dept Elect Engn, Tampa, FL 33420 USA
关键词
Type-4; wind; phase-locked loop (PLL); torsional interaction; low-frequency oscillations; subsynchronous oscillations; STABILITY; DYNAMICS; TURBINES;
D O I
10.1109/TPWRS.2019.2924412
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Oscillations have been observed in wind farms with weak grid interconnections. While Texas observes 4 Hz low-frequency oscillations, the west region in China observes subsynchronous oscillations at 30 Hz. Furthermore, this oscillation mode caused torsional interactions with a remote synchronous generator and led to shutdown of the power plant. Inspired by those real-world events, this paper aims to present an analytical model of type-4 wind in weak grids that can demonstrate both low-frequency and subsynchronous frequency oscillations. Critical factors, e.g., the parameters of the phase-locked loop (PLL), are examined using small-signal analysis. The analysis results are validated using a testbed built in MATLAB/SimPowerSystems. Except power electronic switching sequences, the testbed has controls (e.g., wind turbine pitch control, maximum power point control, converter controls), machine dynamics and power system dynamics modeled. This testbed includes a 100 MW Type-4 wind farm, a 600 MW synchronous generator, a long transmission line and a grid. The testbed successfully demonstrates two types of dominant oscillations under different PLLs. In addition, the testbed demonstrates torsional interactions due to the proximity of the subsynchronous mode and one of the torsional modes.
引用
收藏
页码:109 / 118
页数:10
相关论文
共 26 条
[1]   Modeling, Analysis, and Suppression of the Impact of Full-Scale Wind-Power Converters on Subsynchronous Damping [J].
Alawasa, Khaled Mohammad ;
Mohamed, Yasser Abdel-Rady I. ;
Xu, Wilsun .
IEEE SYSTEMS JOURNAL, 2013, 7 (04) :700-712
[2]  
[Anonymous], 1995, IEEE Trans. on Power Apparatus and Systems, V104, P1057
[3]  
[Anonymous], POWER SYSTEM STABILI
[4]  
Fan L., 2017, CONTROL DYNAMICS POW
[5]   Modeling Type-4 Wind in Weak Grids [J].
Fan, Lingling .
IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, 2019, 10 (02) :853-864
[6]   Wind in Weak Grids: 4 Hz or 30 Hz Oscillations? [J].
Fan, Lingling ;
Miao, Zhixin .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2018, 33 (05) :5803-5804
[7]   An Explanation of Oscillations Due to Wind Power Plants Weak Grid Interconnection [J].
Fan, Lingling ;
Miao, Zhixin .
IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, 2018, 9 (01) :488-490
[8]   Inertia Provision and Estimation of PLL-Based DFIG Wind Turbines [J].
He, Wei ;
Yuan, Xiaoming ;
Hu, Jiabing .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2017, 32 (01) :510-521
[9]   Small Signal Dynamics of DFIG-Based Wind Turbines During Riding Through Symmetrical Faults in Weak AC Grid [J].
Hu, Jiabing ;
Wang, Bo ;
Wang, Weisheng ;
Tang, Haiyan ;
Chi, Yongning ;
Hu, Qi .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 2017, 32 (02) :720-730
[10]   Small Signal Instability of PLL-Synchronized Type-4 Wind Turbines Connected to High-Impedance AC Grid During LVRT [J].
Hu, Jiabing ;
Hu, Qi ;
Wang, Bo ;
Tang, Haiyan ;
Chi, Yongning .