Active arc suppression device based on voltage-source convertor with consideration of line impedance in distribution networks

被引:3
作者
Fan, Bishuang [1 ]
Ma, Haihang [1 ]
Wang, Wen [1 ]
Yao, Ganzhou [1 ]
Li, Qikai [1 ]
Zeng, Xiangjun [1 ]
Guerrero, Josep M. [2 ]
机构
[1] Changsha Univ Sci & Technol, Sch Elect & Informat Engn, Changsha 410114, Peoples R China
[2] Aalborg Univ, Dept Energy Technol, Aalborg, Denmark
关键词
CLOSED-LOOP CONTROL; CONTROL DESIGN; COMPENSATION; INVERTER;
D O I
10.1049/pel2.12203
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In the non-effectively grounding distribution system, residual current under single-line-to-ground (SLG) fault threatens the safety of human being and power supply equipment. Active arc suppression device has been proved to be effective for SLG fault arc suppression when the line impedance is ignored. However, in practice, line impedance varies with the fault location and the load current flowing through the impedance brings about additional voltage drop, which increases the fault current and is not dealt with by the conventional methods. To achieve accurate SLG fault arc suppression with the existence of line impedance, the neutral-to-ground voltage reference for full ground-fault current compensation is firstly derived and a detection method is then proposed. The pre-fault and post-fault line currents are used to eliminate the influence of load current on the line impedance voltage drop. A dual-loop voltage and current controller is then designed. The prototype of active arc suppression device was developed. The results of simulation and prototype experiment validate the effectiveness of the proposed method.
引用
收藏
页码:2585 / 2596
页数:12
相关论文
共 22 条
  • [1] Root-Cause Identification of Single Line-to-Ground Fault in Urban Small Current Grounding Systems Based on Correlation Dimension and Average Resistance
    Cong, Zihan
    Liu, Yadong
    Fang, Jian
    Wang, Peng
    Guo, Linhui
    Jiang, Xiuchen
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2020, 35 (04) : 1834 - 1843
  • [2] Principle and Control Design of a Novel Hybrid Arc Suppression Device in Distribution Networks
    Fan, Bishuang
    Yao, Ganzhou
    Wang, Wen
    Zeng, Xiangjun
    Guerrero, Josep M.
    Yu, Kun
    Zhuo, Chao
    [J]. IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2022, 69 (01) : 41 - 51
  • [3] Faulty phase recognition method based on phase-to-ground voltages variation for neutral ungrounded distribution networks
    Fan, Bishuang
    Yao, Ganzhou
    Wang, Wen
    Yang, Xin
    Ma, Haihang
    Yu, Kun
    Zhuo, Chao
    Zeng, Xiangjun
    [J]. ELECTRIC POWER SYSTEMS RESEARCH, 2021, 190
  • [4] Current closed-loop control and field orientation analysis of an induction motor in six-step operation for railway applications
    Fang, Xiaochun
    Tian, Zhongbei
    Li, Hua
    Yang, Zhongping
    Lin, Fei
    Hillmansen, Stuart
    [J]. IET POWER ELECTRONICS, 2019, 12 (06) : 1462 - 1469
  • [5] Research on Arc-grounding Overvoltage in the 10kV Distribution System
    Feng, Shitao
    Zheng, Lianghua
    Lie, Jianping
    Sun, Youqun
    Chen, Gang
    Ji, Xiaoqiang
    [J]. 2012 INTERNATIONAL CONFERENCE ON FUTURE ENERGY, ENVIRONMENT, AND MATERIALS, PT C, 2012, 16 : 1785 - 1791
  • [6] DC-link voltage control strategy for reducing capacitance and total harmonic distortion in single-phase grid-connected photovoltaic inverters
    Hu, Yihua
    Du, Yang
    Xiao, Weidong
    Finney, Stephen
    Cao, Wenping
    [J]. IET POWER ELECTRONICS, 2015, 8 (08) : 1386 - 1393
  • [7] Faulty feeder detection by adjusting the compensation degree of arc-suppression coil for distribution network
    Huang, Chun
    Tang, Tao
    Jiang, Yajun
    Hua, Leng
    Hong, Chen
    [J]. IET GENERATION TRANSMISSION & DISTRIBUTION, 2018, 12 (04) : 807 - 814
  • [8] Optimum distribution network operation considering distributed generation mode of operations and safety margin
    Ing, Koong Gia
    Jamian, Jasrul Jamani
    Mokhlis, Hazlie
    Illias, Hazlee Azil
    [J]. IET RENEWABLE POWER GENERATION, 2016, 10 (08) : 1049 - 1058
  • [9] Jorgensen H.J., 2005, CIRED 2005, P1
  • [10] Comparison of three-phase three-level voltage source inverter with intermediate dc-dc boost converter and quasi-Z-source inverter
    Panfilov, Dmitry
    Husev, Oleksandr
    Blaabjerg, Frede
    Zakis, Janis
    Khandakji, Kamal
    [J]. IET POWER ELECTRONICS, 2016, 9 (06) : 1238 - 1248