Breakdown Voltage of Transformer Oil Containing Cellulose Particle Contamination With and Without Bridge Formation Under Lightning Impulse Stress

被引:5
作者
Bin Saaidon, Sarizan [1 ,2 ]
Talib, Mohd Aizam [3 ]
Rohani, Mohamad Nur Khairul Hafizi [4 ]
Muhamad, Nor Asiah [1 ,5 ]
Jamil, Mohamad Kamarol Mohd [1 ]
机构
[1] Univ Sains Malaysia, Sch Elect & Elect Engn, Engn Campus, Nibong Tebal 14300, Pulau Pinang, Malaysia
[2] Ctr Instructor & Adv Skill Training, Shah Alam 40300, Selangor, Malaysia
[3] TNB Res Sdn Bhd Res Inst Area, Kajang 43000, Selangor, Malaysia
[4] Univ Malaysia Perlis, Fac Elect Engn Technol, Perlis 02600, Malaysia
[5] Univ Teknol Brunei, Fac Engn, BE-1410 Gadong, Brunei
关键词
Quasi-uniform field; cellulose particle bridging; breakdown voltage; lightning impulse stress; IMPREGNATED PAPER; ESTER; DC; MODEL;
D O I
10.1109/ACCESS.2021.3124098
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
This study investigates the effect of cellulose bridge formation on insulating oil. Such effect influences the breakdown voltage and strength of mineral oil (MO) under standard lightning impulse (LI) voltage. A cylindrical test vessel fitted with spherical-spherical electrodes with a 2 mm gap distance between them was used to generate a quasi-uniform field and observe bridge formation between the gaps. A positive LI waveform (1.2/50 mu s) generated by an impulse generator was applied during the breakdown tests. The rising-voltage method was used to measure the breakdown voltage in accordance with the IEC 60897 standard test method. Weibull cumulative breakdown probability was applied to present the breakdown results statistically, and the outcome was compared with clean oil (CO). Commercial cellulose microcrystalline particles were dispersed into the transformer oil to act as bridge. The concentrations of the samples were 0.004%, 0.008% and 0.012% by weight. The breakdown test results showed that the cellulosic particles reduced the LI breakdown voltage (LIBV) of MO by up to 10%. The influence of cellulose particles on LIBV was also more prominent during bridge formation, with a further reduction of 14%. Evidently, the presence of the cellulose bridge exerted a detrimental effect on the breakdown voltage of MO under LI stress, yielding a reduction of 24% and 27% at 0.004 wt% and 0.012 wt%, respectively. Finite element analysis also indicated that the electrical field strength of cellulosic particle contamination of 0.004 wt% and 0.012 wt% without a bridge skeleton exceeded the critical electric field strength of CO by 20% and 61%, respectively. The presence of cellulosic contamination at any concentration, i.e. either with or without a bridge structure, clearly decreased the breakdown strength of transformer oil. However, the breakdown is not occurred instantaneously. The LI breakdown was initiated and established only at a certain impulse stress level, when the electric field strength along the bridge lines exceeded the critical electric field strength of the oil. Thus, this finding potentially contributes to the formulation of guidelines for condition assessment and contamination monitoring to minimise common issues in power transformer failures that are attributable to the insulation system, and consequently, achieve optimum transformer insulation integrity.
引用
收藏
页码:147994 / 148003
页数:10
相关论文
共 37 条
[1]   Photoluminescence Spectroscopy Measurements for Effective Condition Assessment of Transformer Insulating Oil [J].
Alshehawy, Abdelrahman M. ;
Mansour, Diaa-Eldin A. ;
Ghali, Mohsen ;
Lehtonen, Matti ;
Darwish, Mohamed M. F. .
PROCESSES, 2021, 9 (05)
[2]  
[Anonymous], 2000, EFFECT PARTICLES TRA, V12
[3]  
[Anonymous], 2012, NYTRO GEMINI X HIGH
[4]   THE MOVEMENT OF A CONDUCTING PARTICLE IN TRANSFORMER OIL IN AC FIELDS [J].
BIRLASEKARAN, S .
IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1993, 28 (01) :9-17
[5]  
Ghoneim S. S. M., 2021, PROCESSES, V9, P16
[6]   Enhancing Diagnostic Accuracy of Transformer Faults Using Teaching-Learning-Based Optimization [J].
Ghoneim, Sherif S. M. ;
Mahmoud, Karar ;
Lehtonen, Matti ;
Darwish, Mohamed M. F. .
IEEE ACCESS, 2021, 9 :30817-30832
[7]   Influence of natural ester on frequency dielectric response of impregnated insulation pressboard [J].
Hao, J. ;
Liao, R. ;
Ma, Z. ;
Yang, L. .
IET SCIENCE MEASUREMENT & TECHNOLOGY, 2012, 6 (06) :403-411
[8]  
International Electrotechnical Commission, 1987, 60897 IEC
[9]  
International Electrotechnical Commission, 2001, 600763 IEC
[10]  
Judendorfer T., 2011, 2011 IEEE 17th International Conference on Dielectric Liquids (ICDL 2011), DOI 10.1109/ICDL.2011.6015456