Improved indoor air temperature and humidity control using a novel direct-expansion-based air conditioning system

被引:12
作者
Yang, Liu [1 ]
Deng, Shiming [1 ]
Fang, Guanyu [1 ]
Li, Weilin [2 ]
机构
[1] Hong Kong Polytech Univ, Dept Bldg Serv Engn, Hong Kong, Peoples R China
[2] Zhengzhou Univ, Sch Civil Engn, Sci Ave 100, Zhengzhou 450001, Peoples R China
来源
JOURNAL OF BUILDING ENGINEERING | 2021年 / 43卷
关键词
Direct expansion; Air conditioning; Two sectioned cooling coil; Controllability test; Humidity control; OPERATIONAL CHARACTERISTICS; CAPACITY CONTROLLER; CONTROL ALGORITHMS; PERFORMANCE; EQUIPMENT;
D O I
10.1016/j.jobe.2021.102920
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Many approaches have been tried to obtain an improved indoor thermal environment in small-to medium-sized buildings located in hot-humid climates when using direct-expansion (DX)-based air conditioning (A/C) systems. However, inadequacies still existed in these approaches. Therefore, to address these problems, a novel DX-based A/C system with a two sectioned cooling coil (TS-DXAC) has been proposed. In this paper, a control strategy to operate the TS-DXAC system for achieving an improved indoor air temperature and humidity control in hot and humid climates is presented. Firstly, the detailed configurations of the TS-DXAC system and the control strategy of the TS-DXAC system are presented. The developed strategy included two control algorithms, i.e., Algorithm I and Algorithm II, enabling the TS-DXAC system to be operated under two different indoor conditions, i.e., hot-humid, and hot-dry, respectively. Secondly, a test TS-DXAC system was set up and the controllability tests for the control strategy were carried out. This is followed by presenting the experimental results and related discussions. The experimental results demonstrated that in all the tests, indoor air temperature could be directly controlled at the two indoor conditions, while indoor air temperature and relative humidity could be simultaneously controlled over a relatively long period at a hot-humid indoor condition using Algorithm I. The control strategy enabled the TS-DXAC system to respond the changes in either indoor settings or cooling loads by outputting variable sensible and latent cooling capacities at a higher energy efficiency compared to conventional On-Off controlled DX A/C systems. However, to improve the control sensitivity under Algorithm I, consideration should be given to the variable speed operation of the compressor in the TS-DXAC system.
引用
收藏
页数:12
相关论文
共 50 条
  • [21] A novel hybrid steady-state model based controller for simultaneous indoor air temperature and humidity control
    Xu Xiangguo
    Deng Shiming
    Han Xiaohong
    Zhang Xuejun
    ENERGY AND BUILDINGS, 2014, 68 : 593 - 602
  • [22] Model predictive control of indoor thermal environment conditioned by a direct expansion air conditioning system
    Yudong Xia
    Ming Zhu
    Aipeng Jiang
    Jian Wang
    Xiaoxia Bai
    Shiming Deng
    Building Simulation, 2023, 16 : 357 - 378
  • [23] Improving degree of superheat control in a direct expansion (DX) air conditioning (A/C) system
    Qi, Qi
    Deng, Shiming
    Xu, Xiangguo
    Chan, M. Y.
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2010, 33 (01): : 125 - 134
  • [24] An experimental investigation on the operational characteristics of a novel direct expansion based air conditioning system with a two-sectioned cooling coil
    Yang, Liu
    Yan, Huaxia
    Deng, Shiming
    Li, Weilin
    INTERNATIONAL JOURNAL OF REFRIGERATION, 2020, 118 (118) : 131 - 138
  • [25] A Thermal Comfort based Controller for a Direct Expansion Air Conditioning System
    Yan, Huaxia
    Niu, Jiajia
    Deng, Shiming
    PROCEEDINGS OF THE 9TH INTERNATIONAL CONFERENCE ON APPLIED ENERGY, 2017, 142 : 1817 - 1822
  • [26] A DDC-based capacity controller of a direct expansion (DX) air conditioning (A/C) unit for simultaneous indoor air temperature and humidity control - Part I: Control algorithms and preliminary controllability tests
    Li, Zheng
    Deng, Shiming
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2007, 30 (01): : 113 - 123
  • [27] A control-oriented semi-physical model for a direct expansion air conditioning system
    Xu Xiangguo
    Deng Shiming
    Han Xiaohong
    Zhang Xuejun
    BUILDING SERVICES ENGINEERING RESEARCH & TECHNOLOGY, 2014, 35 (06) : 585 - 599
  • [28] An autonomous hierarchical control for improving indoor comfort and energy efficiency of a direct expansion air conditioning system
    Mei, Jun
    Xia, Xiaohua
    Song, Mengjie
    APPLIED ENERGY, 2018, 221 : 450 - 463
  • [29] Automatic temperature and humidity control system using air-conditioning in transformer substation
    Feng, Li
    Hui, Zhou
    Yan, Tao
    2012 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2012,
  • [30] Influence of Temperature and Humidity Control in Air Conditioning on Indoor Environment Quality and Human Feelings
    Sun, Yuping
    Zhu, Neng
    ADVANCES IN CIVIL ENGINEERING II, PTS 1-4, 2013, 256-259 : 2648 - 2651