METHODOLOGY FOR TRANSMISSION LINE CAPACITY ASSESSEMENT BASED ON PMU DATA

被引:0
作者
Mutule, Anna [1 ]
Grebesh, Ervin [1 ]
Oleinikova, Irina [1 ]
Obushevs, Artjoms [1 ]
机构
[1] Inst Phys Energet, Smart Grid Res Ctr, Riga, Latvia
来源
2016 POWER SYSTEMS COMPUTATION CONFERENCE (PSCC) | 2016年
关键词
Conductor temperature; dynamic line rating (DLR); line sag; phasor measurement unit (PMU);
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This paper reflects the authors' experience in conductor thermal part (temperature) and mechanical part (sag and clearance) estimation in real Latvian PS conditions using IEEE, CIGRE, Girshin and classical mechanics methods. Both theoretical and practical results of the research are discussed. Theoretical calculations based on real Phasor Measurement Unit (PMU) measurements of 330 kV line and environmental data collected from meteo-websites have shown that deviation is low in conductor thermal calculation methods. The Dynamic Line Rating (DLR) measurements are improved with the PMU data, which permit accurate line current data with GPS timestamps. The authors have calculated the conditions of conductor thermal dynamics at a step of one second; such accuracy together with environmental data can provide an excess of maximum line capacity without harming the conductor life cycle.
引用
收藏
页数:5
相关论文
共 11 条
[1]  
[Anonymous], 2007, THERM BEH OV COND
[2]  
[Anonymous], 1969, 88525 LATV TSO
[3]  
CIGRE, 2006, GUID SEL WEATH PAR B
[4]  
Engelis A., 2004, HIGH VOLTAGE ELECT L
[5]  
Girshin S. S., 2014, MODERN PROBLEMS SCI
[6]  
*IEEE, 2007, 7382006 IEEE
[7]  
Kosterev D., TRANSMISSION DI 0114, P44
[8]  
Krykov K., 1979, DESIGN MECH CALCULAT
[9]   Experimentally validated partial least squares model for dynamic line rating [J].
Morrow, David John ;
Fu, Jiao ;
Abdelkader, Sobhy Mohamed .
IET RENEWABLE POWER GENERATION, 2014, 8 (03) :260-268
[10]  
Oleinikova I., 2015, INT C POW ENG EN EL, P453