Maldistribution in air-water heat pump evaporators. Part 1: Effects on evaporator, heat pump and system level

被引:10
作者
Mader, Gunda [1 ]
Palm, Bjorn [2 ]
Elmegaard, Brian [3 ]
机构
[1] Danfoss AS Refrigerat & Air Conditioning, Nordborg, Denmark
[2] Royal Inst Technol, Dept Energy Technol, Div Appl Thermodynam & Refrigerat, Stockholm, Sweden
[3] Tech Univ Denmark, Dept Mech Engn, DK-2800 Lyngby, Denmark
来源
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID | 2015年 / 50卷
关键词
Heat pump; Maldistribution; Annual performance; System modeling; Operating costs; FLOW MALDISTRIBUTION; 2-PHASE FLOW; PERFORMANCE;
D O I
10.1016/j.ijrefrig.2014.07.006
中图分类号
O414.1 [热力学];
学科分类号
摘要
This paper presents an approach to quantify the effect of evaporator maldistribution on operating costs of air water heat pumps. In the proposed simulation model maldistribution is induced by two parameters describing refrigerant phase and air flow distribution. Annual operating costs are calculated based on heat pump performance at distinct operating conditions. Results show that percentage increase of operating costs is similar for the three considered climate zones, even though the effect of maldistribution on heat pump performance varies with operating conditions. Differences in terms of absolute cost increase for the climate zones arise mainly due to a varying number of operating hours. Absolute cost increase is considerable in the average and especially colder climate zone and can only partly be reduced by enlarging the evaporator. (C) 2014 Elsevier Ltd and IIR. All rights reserved.
引用
收藏
页码:207 / 216
页数:10
相关论文
共 25 条
  • [21] Effect of the header pressure drop induced flow maldistribution on the microchannel evaporator performance
    Tuo, Hanfei
    Hrnjak, Pega
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2013, 36 (08): : 2176 - 2186
  • [22] Verein Deutscher Ingenieure VDI-Gesellschaft Verfahrenstechnik und Chemieingenieurwesen (GVC), 2006, VDI WARMEATLAS
  • [23] Two-phase flow distribution in compact heat exchanger manifolds
    Vist, S
    Pettersen, J
    [J]. EXPERIMENTAL THERMAL AND FLUID SCIENCE, 2004, 28 (2-3) : 209 - 215
  • [24] Winter J., 2012, KI KALTE LUFT KLIMAT, V11, P21
  • [25] Performance Evaluation and Optimization of A Refrigerant Distributor for Air Conditioner
    Yoshioka, Shun
    Kim, Hyunyoung
    Kasai, Kazushige
    [J]. JOURNAL OF THERMAL SCIENCE AND TECHNOLOGY, 2008, 3 (01): : 68 - 77