Insulator icing test methods, selection criteria and mitigation alternatives

被引:16
作者
Farzaneh, M. [1 ]
Chisholm, W. A.
机构
[1] Univ Quebec, Engn Power Network Atmospher Icing, Atmospher Icing Power Network Equipment, NSERC, Chicoutimi, PQ, Canada
[2] Kinectr, Toronto, ON, Canada
关键词
climate; contamination; flashover; fog; high voltage; ice; insulation coordination; snow; line insulators; test methods;
D O I
10.1109/TDEI.2007.4401229
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
IEEE-PES Task Forces on insulator icing have been active since 1999 in developing icing test methods and recommending insulator selection criteria. Progress towards this goal included methods for obtaining reproducible results and also modeling of important factors. This paper reports on the progress and work accomplished by the PES Task Forces, serving as input data to the joint DEIS/PES task force work initiated recently to expand the technical basis of the existing knowledge. In selecting adequate insulators for substations and lines at distribution and transmission voltage levels, special measures may be needed in locations exposed to freezing conditions. The environmental and insulator parameters that influence the risk of flashover are noted. The selection process and mitigation options, based on these environmental parameters, are then described. The selection criteria include insulator size, shape, surface material, surface quality, electric field improvement, and orientation.
引用
收藏
页码:1462 / 1473
页数:12
相关论文
共 59 条
[1]  
[Anonymous], NATL ATMOSPHERIC DEP
[2]  
[Anonymous], 60071 IEC
[3]  
*ANSI, 2001, C22002 ANSI
[4]   FLASHOVER TESTS OF ARTIFICIALLY ICED INSULATORS [J].
CHARNESKI, MD ;
GAIBROIS, GL ;
WHITNEY, BF .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1982, 101 (08) :2429-2433
[5]   FLASHOVER PERFORMANCE OF ARTIFICIALLY CONTAMINATED AND ICED LONG-ROD TRANSMISSION-LINE INSULATORS [J].
CHERNEY, EA .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1980, 99 (01) :46-52
[6]  
Chisholm W. A., 2000, 2 INT WORKSH HIGH VO
[7]   The cold-fog test [J].
Chisholm, WA ;
Ringler, KG ;
Erven, CC ;
Green, MA ;
Melo, O ;
Tam, Y ;
Nigol, O ;
Kuffel, J ;
Boyer, A ;
Pavasars, IK ;
Macedo, FX ;
Sabiston, JK ;
Caputo, RB .
IEEE TRANSACTIONS ON POWER DELIVERY, 1996, 11 (04) :1874-1880
[8]  
*CIGRE TASK FORC, 1999, ELECTRA, P91
[9]  
CIGRE Task Force 33.04.09, 2000, ELECTRA, V188, P55
[10]  
*CIGRE TF, 2000, POLL INS REV CURR KN