Impact of orthophosphate on lead release from pipe scale in high pH, low alkalinity water

被引:29
作者
Bae, Yeunook [1 ]
Pasteris, Jill D. [2 ]
Giammar, Daniel E. [1 ]
机构
[1] Washington Univ, Dept Energy Environm & Chem Engn, St Louis, MO 63130 USA
[2] Washington Univ, Dept Earth & Planetary Sci, St Louis, MO 63130 USA
基金
美国国家科学基金会;
关键词
Lead; Corrosion control; Orthophosphate; Phosphohedyphane; Fluorapatite; GALVANIC CORROSION; CHLORINE; DISSOLUTION; CHEMISTRY; PHOSPHATE; OXIDES; IRON;
D O I
10.1016/j.watres.2020.115764
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
This study explored the ability of orthophosphate addition to limit lead release from lead service lines delivering high pH, low alkalinity water. We built pipe loop reactors with lead pipes harvested from Providence, RI, and we operated them with high pH and low alkalinity water of a composition similar to that in Providence. Orthophosphate addition decreased the release of both dissolved and particulate lead to the water. The most substantial decreases in total lead concentrations occurred after 15 weeks of orthophosphate addition, which was associated with the formation of calcium-lead-phosphorus (Ca-Pb-P) solids as part of the pipe scale. Pre-existing hydrocerussite (Pb-3(CO3)(2)(OH)(2(s))) in the scale of the lead pipe appeared to promote the formation of a Ca-Pb-P solid similar to phosphohedyphane (Ca2Pb3(-PO4)(3)(CI,F,OH)((s))). Continuous orthophosphate addition was also associated with the formation of a calcium phosphate solid with features like those of fluorapatite (Ca-5(PO4)(3)F-(s)) on the outermost layer of the scale. Through promoting the formation of these new solids within and on top of the scales, orthophosphate addition limited release of dissolved and particulate lead. These results demonstrate the ability of orthophosphate to control lead release at higher pH conditions than those for which it has typically been used. In addition to the formation of phosphate solids, PbO2(s), which was not present on the as-received pipes, was formed due to the constant supply of free chlorine in the laboratory-scale experiment. (C) 2020 Elsevier Ltd. All rights reserved.
引用
收藏
页数:11
相关论文
共 40 条
[1]  
[Anonymous], 2016, EPA 816B16003. USEPA Office of Water (4606M)
[2]  
[Anonymous], 2005, Standard Methods for the Examination of Water and Wastewater
[3]  
[Anonymous], 2011, Australian drinking water guidelines
[4]   The Ability of Phosphate To Prevent Lead Release from Pipe Scale When Switching from Free Chlorine to Monochloramine [J].
Bae, Yeunook ;
Pasteris, Jill D. ;
Giammar, Daniel E. .
ENVIRONMENTAL SCIENCE & TECHNOLOGY, 2020, 54 (02) :879-888
[5]   Surface analysis and depth profiling of corrosion products formed in lead pipes used to supply low alkalinity drinking water [J].
Davidson, CM ;
Peters, NJ ;
Britton, A ;
Brady, L ;
Gardiner, PHE ;
Lewis, BD .
WATER SCIENCE AND TECHNOLOGY, 2004, 49 (02) :49-54
[6]   Source and occurrence of particulate lead in tap water [J].
Deshommes, Elise ;
Laroche, Laurent ;
Nour, Shokoufeh ;
Cartier, Clement ;
Prevost, Michele .
WATER RESEARCH, 2010, 44 (12) :3734-3744
[7]  
Edwards M, 2004, J AM WATER WORKS ASS, V96, P69
[8]   Experience in Wales (UK) of the optimisation of orthophosphate dosing for controlling lead in drinking water [J].
Hayes, C. R. ;
Incledion, S. ;
Balch, M. .
JOURNAL OF WATER AND HEALTH, 2008, 6 (02) :177-185
[9]  
Health Canada, 2019, GUID CAN DRINK WAT Q
[10]   Formation of Pb(IV) oxides a in chlorinated water [J].
Lytle, DA ;
Schock, MR .
JOURNAL AMERICAN WATER WORKS ASSOCIATION, 2005, 97 (11) :102-114