Thermodynamic model development, experimental validation and performance analysis of a MW CCHP system integrated with dehumidification system

被引:22
作者
Jiang, Runhua [1 ]
Han, Wei [2 ]
Qin, Frank G. F. [1 ]
Sui, Jun [2 ]
Yin, Huibin [1 ]
Yang, Minlin [1 ]
Xu, Yongjun [1 ]
机构
[1] Dongguan Univ Technol, Sch Chem Engn & Energy Technol, Guangdong Prov Key Lab Distributed Energy Syst, Dongguan 523808, Peoples R China
[2] Chinese Acad Sci, Inst Engn Thermophys, POB 2706, Beijing 100190, Peoples R China
基金
中国国家自然科学基金;
关键词
A MW CCHP system; Dehumidification; Thermodynamic model; Validation; Performance analysis; INTERNAL-COMBUSTION ENGINES; POWER-SYSTEM; MICRO-CCHP; DECISION-MAKING; EXERGY ANALYSES; COMBINED HEAT; DRIVEN; ENERGY; OPTIMIZATION; GENERATION;
D O I
10.1016/j.enconman.2017.12.060
中图分类号
O414.1 [热力学];
学科分类号
摘要
Combined cooling, heating and power (CCHP) systems, which have the advantages of energy saving and environmental protection, have attracted more and more attentions. Great deals of works have been done, but most of them are theoretical research. It is still lack of experimental research for large scale CCHP system in practical application, and an overall off-design thermodynamic model is also desired to simulate or exam the system performance. In this work, a novel CCHP system integrated with dehumidification system is proposed for further utilizing waste heat, in which an internal combustion engine (ICE) is used as prime mover, its heat of flue gas and the heat of jacket water above 81 degrees C are used to drive absorption chiller, and the heat of jacket water below 81 degrees C is used to drive absorption dehumidifier. A comprehensive off-design thermodynamic model and evaluation of the system is established. The tested results of a MW CCHP system integrated with dehumidification system are used to validate the model, and the thermodynamic performance analysis is also carried out. The thermodynamic performance comparison between the CCHP system integrated with dehumidification system and conventional CCHP system has been done. The results show that: the simulated values are basically in keeping with those experimental results; when the output power of ICE is 1200 kW, the primary energy rate of the MW CCHP system can go up to 84.0%, the primary energy saving ratio achieves 32.77%, and exergy efficiency is 42.45%; the thermodynamic performance of the proposed CCHP system is better than conventional CCHP system.
引用
收藏
页码:176 / 185
页数:10
相关论文
共 50 条
  • [21] Performance evaluation of a novel CCHP system integrated with MCFC, ISCC and LiBr refrigeration system
    Lu, Ziyi
    Duan, Liqiang
    Wang, Zhen
    INTERNATIONAL JOURNAL OF HYDROGEN ENERGY, 2022, 47 (48) : 20957 - 20972
  • [22] Thermodynamic analyses and optimization of a novel CCHP system integrated organic Rankine cycle and solar thermal utilization
    Wu, Di
    Zuo, Jifeng
    Liu, Zhijian
    Han, Zhonghe
    Zhang, Yulong
    Wang, Qiaomei
    Li, Peng
    ENERGY CONVERSION AND MANAGEMENT, 2019, 196 : 453 - 466
  • [23] Thermodynamic performance analysis of a fuel cell trigeneration system integrated with solar-assisted methanol reforming
    Wang, Jiangjiang
    Wu, Jing
    Xu, Zilong
    Li, Meng
    ENERGY CONVERSION AND MANAGEMENT, 2017, 150 : 81 - 89
  • [24] Performance enhancement of a humidification-dehumidification desalination system A thermodynamic investigation
    Tlili, Iskander
    Osman, M.
    Barhoumi, E. M.
    Alarifi, I.
    Abo-Khalil, Ahmed G.
    Praveen, R. P.
    Sayed, Khairy
    JOURNAL OF THERMAL ANALYSIS AND CALORIMETRY, 2020, 140 (01) : 309 - 319
  • [25] Thermodynamic and economic analysis of solar assisted CCHP-ORC system with DME as fuel
    Wang, Shucheng
    Fu, Zhongguang
    ENERGY CONVERSION AND MANAGEMENT, 2019, 186 : 535 - 545
  • [26] Performance Analysis of an Integrated Solar Dehumidification System with HVAC in A Typical Corner Store in the USA
    Almehmadi, Fahad A.
    Hallinan, Kevin P.
    SUSTAINABILITY, 2020, 12 (10)
  • [27] Sensitivity analysis of energy demands on performance of CCHP system
    Li, C. Z.
    Shi, Y. M.
    Huang, X. H.
    ENERGY CONVERSION AND MANAGEMENT, 2008, 49 (12) : 3491 - 3497
  • [28] Economic performance study of the integrated MR-SOFC-CCHP system
    Hou, Qinlong
    Zhao, Hongbin
    Yang, Xiaoyu
    ENERGY, 2019, 166 : 236 - 245
  • [29] Performance analysis of solar-integrated ejector-based CCHP system for a commercial building
    Saladi, Joshua Kumar
    Suresh, Ronanki
    Datta, Santanu Prasad
    SUSTAINABLE CHEMISTRY FOR CLIMATE ACTION, 2025, 6
  • [30] Prime Mover Capacity Optimization and Thermodynamic Performance Analysis of Internal Combustion Engine Based CCHP System
    Shucheng Wang
    Imran Muhammad
    Hongwei Li
    Xiaoxu Chen
    Mei Qin
    Journal of Thermal Science, 2023, 32 : 1583 - 1594