Incorporating superconducting fault current limiters in the probabilistic evaluation of transient recovery voltage

被引:10
作者
Faried, S. O. [1 ]
Elsamahy, M. [1 ]
机构
[1] Univ Saskatchewan, Power Syst Res Grp, Saskatoon, SK S7N 5A9, Canada
关键词
CIRCUIT-BREAKERS; INDUCTIVE FCL; LINES; SYSTEM; IMPACT;
D O I
10.1049/iet-gtd.2010.0312
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A Monte Carlo based approach to evaluate the transient recovery voltages (TRVs) induced across circuit breaker poles during clearing faults on transmission lines equipped with a superconducting fault current limiter is presented here. In this context, investigations have been conducted on a sample power system model taking into consideration the uncertainty of several factors associated with the practical operation of a power system. Risk indices that reflect the likelihood that the TRV induced across a circuit breaker poles as well as its rate of rise exceed their design values are also presented. The EMTP-RV (Electro Magnetic Transients Program) was used in the simulation studies.
引用
收藏
页码:101 / 107
页数:7
相关论文
共 25 条
[21]  
Papoulis A., 1984, PROBABILITY RANDOM V
[22]   TOWARDS THE SUPERCONDUCTING FAULT CURRENT LIMITER [J].
THURIES, E ;
PHAM, VD ;
LAUMOND, Y ;
VERHAEGE, T ;
FEVRIER, A ;
COLLET, M ;
BEKHALED, M .
IEEE TRANSACTIONS ON POWER DELIVERY, 1991, 6 (02) :801-808
[23]   Reducing voltage sags through fault current limitation [J].
Tosato, F ;
Quaia, S .
IEEE TRANSACTIONS ON POWER DELIVERY, 2001, 16 (01) :12-17
[24]  
WILSON DD, 1973, IEEE T POWER APPARAT, V73, P1050
[25]  
2010, ELECTRA