Association between substandard classroom ventilation rates and students' academic achievement

被引:211
作者
Haverinen-Shaughnessy, U. [1 ,2 ]
Moschandreas, D. J. [3 ]
Shaughnessy, R. J. [1 ]
机构
[1] Univ Tulsa, Indoor Air Program, Tulsa, OK 74104 USA
[2] Natl Inst Hlth & Welf, Dept Environm Hlth, Kuopio, Finland
[3] IIT, Dept Civil Architectural & Environm Engn, Chicago, IL 60616 USA
基金
芬兰科学院;
关键词
Academic performance; Carbon dioxide; Indoor air quality; Mathematics; Reading; Schools; CLASS SIZE; PERFORMANCE; SCHOOLS; CHILDREN; QUALITY; HEALTH; GAINS; WORK;
D O I
10.1111/j.1600-0668.2010.00686.x
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
P>This study focuses on the relationship between classroom ventilation rates and academic achievement. One hundred elementary schools of two school districts in the southwest United States were included in the study. Ventilation rates were estimated from fifth-grade classrooms (one per school) using CO2 concentrations measured during occupied school days. In addition, standardized test scores and background data related to students in the classrooms studied were obtained from the districts. Of 100 classrooms, 87 had ventilation rates below recommended guidelines based on ASHRAE Standard 62 as of 2004. There is a linear association between classroom ventilation rates and students' academic achievement within the range of 0.9-7.1 l/s per person. For every unit (1 l/s per person) increase in the ventilation rate within that range, the proportion of students passing standardized test (i.e., scoring satisfactory or above) is expected to increase by 2.9% (95%CI 0.9-4.8%) for math and 2.7% (0.5-4.9%) for reading. The linear relationship observed may level off or change direction with higher ventilation rates, but given the limited number of observations, we were unable to test this hypothesis. A larger sample size is needed for estimating the effect of classroom ventilation rates higher than 7.1 l/s per person on academic achievement. Practical Implications The results of this study suggest that increasing the ventilation rates toward recommended guideline ventilation rates in classrooms should translate into improved academic achievement of students. More studies are needed to fully understand the relationships between ventilation rate, other indoor environmental quality parameters, and their effects on students' health and achievement. Achieving the recommended guidelines and pursuing better understanding of the underlying relationships would ultimately support both sustainable and productive school environments for students and personnel.
引用
收藏
页码:121 / 131
页数:11
相关论文
共 33 条
[21]   Teachers, schools, and academic achievement [J].
Rivkin, SG ;
Hanushek, EA ;
Kain, JF .
ECONOMETRICA, 2005, 73 (02) :417-458
[22]  
Sanders W.L., 1996, CUMULATIVE RESIDUAL
[23]   WHAT REALLY MATTERS IN 2ND LANGUAGE-LEARNING FOR ACADEMIC-ACHIEVEMENT [J].
SAVILLETROIKE, M .
TESOL QUARTERLY, 1984, 18 (02) :199-219
[24]  
Schulte R, 2005, ASHRAE J, V47, P38
[25]   Ventilation and performance in office work [J].
Seppänen, O ;
Fisk, WJ ;
Lei, QH .
INDOOR AIR, 2006, 16 (01) :28-36
[26]  
SHAUGHNESSY R, 2007, P ASHRAE IAQ HLTH SU
[27]  
Shaughnessy RJ, 2006, INDOOR AIR, V16, P465, DOI 10.1111/j.1600-0668.2006.00440.x
[28]   Associations between classroom CO2 concentrations and student attendance in Washington and Idaho [J].
Shendell, DG ;
Prill, R ;
Fisk, WJ ;
Apte, MG ;
Blake, D ;
Faulkner, D .
INDOOR AIR, 2004, 14 (05) :333-341
[29]   Socioeconomic status and academic achievement: A meta-analytic review of research [J].
Sirin, SR .
REVIEW OF EDUCATIONAL RESEARCH, 2005, 75 (03) :417-453
[30]   New ventilation systems at select schools in Sweden -: Effects on asthma and exposure [J].
Smedje, G ;
Norbäck, D .
ARCHIVES OF ENVIRONMENTAL HEALTH, 2000, 55 (01) :18-25