An experimental study on achieving even-frosting for an air source heat pump using a novel dual-fan outdoor coil

被引:23
作者
Bai, Xiaoxia [1 ]
Liu, Shengnan [1 ]
Deng, Shiming [2 ]
Zhang, Long [3 ]
Wei, Minchen [1 ]
机构
[1] Hong Kong Polytech Univ, Dept Bldg Serv Engn, Hong Kong, Peoples R China
[2] Qatar Univ, Dept Mech & Ind Engn, POB 2713, Doha, Qatar
[3] Beijing Inst Technol, Sch Mech Engn, Dept Energy & Power Engn, Beijing, Peoples R China
关键词
Air source heat pump; Even frosting; Novel dual-fan outdoor coil; Alternate operation; Frosting duration; Defrosting frequency; DEFROSTING CHARACTERISTICS; WATER-RETENTION; PERFORMANCE; SURFACE; UNIT; FIN; TEMPERATURE; EXCHANGER; SYSTEM; GROWTH;
D O I
10.1016/j.enbuild.2021.111695
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Many related studies suggested that a fixed airflow direction usually led to that the most frost would only deposit on the windward side of finned tube heat exchangers (FTHXs) of the traditional single fan outdoor coils in air source heat pumps (ASHPs), result in more frequent defrosting operations and a lower operating efficiency of ASHPs. In this experimental study, to achieve evener frosting on outdoor coils, a novel outdoor coil having two identical fans was proposed. The two fans, Fan A and Fan B, may operate alternately to reverse airflow direction based on a pre-set value of time interval for alternate operation (t(TI)(AO)). Feasibility and stability of the novel dual-fan outdoor coil to achieve even frosting on both windward and leeward sides of the FTHX were experimentally studied via seven experimental cases including both single and multiple frosting-defrosting operation cycles. The experimental results demonstrated that when using the novel dual-fan outdoor coil in Cases 3, 4 and 7, the heating/frosting duration was lengthened by 23.6%, 34.5% and 46.4%, and the averaged output heating capacity ((q) over bar) was increased by 5.5%, 9.5% and 9.6 %, and averaged COP (COP) by 6.7%, 10.5% and 11.1% respectively, and the defrosting frequency was decreased by 33.3% in Case 7,when compared to using the traditional single-fan outdoor coil. Besides, as t(TIAO) values were decreased from 15 mins to 10 mins for both fans, and to 6 mins for Fan A and 8 mins for Fan B, heating/frosting operation duration was increased by 8.9% and 19.4%, respectively, at a higher (q) over bar and C (O) over barP , as compared to those using the traditional single-fan outdoor coil. The experimental results clearly demonstrated that the use of the novel dual-fan outdoor coil can help achieve evener frosting on both sides of the FTHX, and hence a longer heating operation duration and a higher operating efficiency and output heating capacity. (C) 2021 Elsevier B.V. All rights reserved.
引用
收藏
页数:14
相关论文
共 35 条
[1]  
[Anonymous], 2012, GB 50736-2012
[2]   Operating performances of an ASHP unit operated in a mild and humid region using tube-encircled photoelectric sensor based defrosting initiation strategy [J].
Bai, Xiaoxia ;
Wang, Wei ;
Sun, Yuying ;
Liu, Jingdong ;
Ge, Yijing ;
Deng, Shiming .
ENERGY AND BUILDINGS, 2018, 177 :140-153
[3]  
Carlson D.M., 2001, Deposition, distribution, and effects of frost on a multi-row heat exchanger performance
[4]   A techno-economic comparison of ground-coupled and air-coupled heat pump system for space cooling [J].
Esen, Hikmet ;
Inalli, Mustafa ;
Esen, Mehmet .
BUILDING AND ENVIRONMENT, 2007, 42 (05) :1955-1965
[5]   A study of frost build-up on hydrophilic and hydrophobic surfaces under forced convection conditions [J].
Hermes, Christian J. L. ;
Nascimento, Valter S., Jr. ;
Loyola, Felipe R. ;
Cardoso, Rodrigo P. ;
Sommers, Andrew D. .
EXPERIMENTAL THERMAL AND FLUID SCIENCE, 2019, 100 :76-88
[6]   A semi-empirical model for predicting frost accretion on hydrophilic and hydrophobic surfaces [J].
Hermes, Christian J. L. ;
Sommers, Andrew D. ;
Gebhart, Colton W. ;
Nascimento, Valter S., Jr. .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2018, 87 :164-171
[7]   An experimental study on the frosting characteristic and performance of a micro-channel evaporator in an air source heat pump unit [J].
Hu, Wenju ;
Fan, Jin ;
Song, Mengjie ;
Jia, Peng ;
Gao, Yan .
ENERGY AND BUILDINGS, 2020, 224
[8]   Analysis on a hybrid desiccant air-conditioning system [J].
Jia, C. X. ;
Dai, Y. J. ;
Wu, J. Y. ;
Wang, R. Z. .
APPLIED THERMAL ENGINEERING, 2006, 26 (17-18) :2393-2400
[9]   Experimental investigation of frost retardation for superhydrophobic surface using a luminance meter [J].
Kim, Donghee ;
Kim, Hisuk ;
Kim, Sun Woo ;
Kim, Dong Rip ;
Lee, Kwan-Soo .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2015, 87 :491-496
[10]   Local frosting behavior of a plated-fin and tube heat exchanger according to the refrigerant flow direction and surface treatment [J].
Kim, Kyoungmin ;
Kim, Dong Rip ;
Lee, Kwan-Soo .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2013, 64 :751-758