Study on Dehumidification Performance of a Multi-Stage Internal Cooling Solid Desiccant Adsorption Packed Bed

被引:5
作者
Yang, Wansheng [1 ]
Ren, Jiayun [1 ]
Lin, Zhongqi [1 ]
Wang, Zhangyuan [1 ]
Zhao, Xudong [2 ]
机构
[1] Guangdong Univ Technol, Sch Civil & Transportat Engn, Guangzhou 510006, Guangdong, Peoples R China
[2] Univ Hull, Sch Engn, Kingston Upon Hull HU6 7RX, N Humberside, England
基金
国家重点研发计划; 英国工程与自然科学研究理事会; 欧盟地平线“2020”;
关键词
internal cooling; multi-stage adsorption bed; solid desiccant; dehumidification; COATED HEAT-EXCHANGER;
D O I
10.3390/en11113038
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
In this paper, the solid desiccant adsorption packed bed with a three-stage internal cooling (ICSPB) has been proposed to improve the dehumidification efficiency and make a comparison with that of non-internal cooling. To investigate the performance of the ICSPB, the dehumidification capacity, dehumidification efficiency, water content of solid desiccant, moisture ratio of solid desiccant, temperature of solid desiccant and inlet and outlet air temperature difference were discussed in different conditions of inlet air and supplying water temperature. It was found that the dehumidification performance of the bed with internal cooling could be improved greatly in the low temperature and low humidity conditions, while in the high temperature and humid, the improvement was not obvious. With internal cooling, the dehumidification efficiency and the water content of the solid desiccant could be improved 59.69% and 110.7%, respectively, and the temperature of solid desiccant could be reduced 2.2 degrees C when the ICSPB operated at the inlet air temperature of 20 degrees C, inlet humidity of 55%, and water temperature of 14 degrees C. Moreover, the dehumidification performance at each stage of ICSPB was studied. It was found that, the first stage played the most important role in the dehumidification process. In addition, the calculation models that can be used to predict the moisture ratio and the temperature of solid desiccant were established on the test results.
引用
收藏
页数:19
相关论文
共 29 条
  • [1] Reducing the Demand of Energy Cooling in the CED, "Centers of Processing Data", with Use of Free-Cooling Systems
    Cannistraro, G.
    Cannistraro, M.
    Cannistraro, A.
    Galvagno, A.
    Trovato, G.
    [J]. INTERNATIONAL JOURNAL OF HEAT AND TECHNOLOGY, 2016, 34 (03) : 498 - 502
  • [2] Cannistraro G, 2017, INT J HEAT TECHNOL, V35, pS442, DOI 10.18280/ijht.35Sp0160
  • [3] The Applications of the New Technologies "E-Sensing" in Hospitals
    Cannistraro, M.
    Lorenzini, E.
    [J]. INTERNATIONAL JOURNAL OF HEAT AND TECHNOLOGY, 2016, 34 (04) : 551 - 557
  • [4] Cannistraro M., 2018, Mathematical Modelling of Engineering Problems, V5, P197, DOI [10.18280/mmep.050311, DOI 10.18280/MMEP.050311]
  • [5] New sol-gel deposition technique in the Smart-Windows - Computation of possible applications of Smart-Windows in buildings
    Cannistraro, Mauro
    Castelluccio, Maria Elena
    Germano, David
    [J]. JOURNAL OF BUILDING ENGINEERING, 2018, 19 : 295 - 301
  • [6] Experimental results on adsorption beds for air dehumidification
    Finocchiaro, Pietro
    Beccali, Marco
    Gentile, Vincenzo
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2016, 63 : 100 - 112
  • [7] Dehydration of natural gas using solid desiccants
    Gandhidasan, P
    Al-Farayedhi, AA
    Al-Mubarak, AA
    [J]. ENERGY, 2001, 26 (09) : 855 - 868
  • [8] Feasible study of a self-cooled solid desiccant cooling system based on desiccant coated heat exchanger
    Ge, T. S.
    Dai, Y. J.
    Wang, R. Z.
    Li, Y.
    [J]. APPLIED THERMAL ENGINEERING, 2013, 58 (1-2) : 281 - 290
  • [9] Simulation investigation on solar powered desiccant coated heat exchanger cooling system
    Ge, T. S.
    Dai, Y. J.
    Li, Y.
    Wang, R. Z.
    [J]. APPLIED ENERGY, 2012, 93 : 532 - 540
  • [10] Experimental comparison and analysis on silica gel and polymer coated fin-tube heat exchangers
    Ge, T. S.
    Dai, Y. J.
    Wang, R. Z.
    Peng, Z. Z.