Evaluation of various CFD modelling strategies in predicting airflow and temperature in a naturally ventilated double skin facade

被引:120
作者
Pasut, Wilrner [1 ]
De Carli, Michele [2 ]
机构
[1] Univ Calif Berkeley, Ctr Built Environm, Berkeley, CA 94720 USA
[2] Univ Padua, Dipartimento Fis Tecn, I-35131 Padua, Italy
关键词
Double skin facade; CFD; Natural ventilation; Performance simulation; Thermal performance; Air flow; COMPUTATIONAL FLUID-DYNAMICS; SIMULATION; CONVECTION;
D O I
10.1016/j.applthermaleng.2011.11.028
中图分类号
O414.1 [热力学];
学科分类号
摘要
Demands for energy savings, thermal and visual comfort and a high-tech image for new building envelopes can be met with a Double Skin Facade (DSF). These kinds of building envelopes are widely encouraged, proposed and increasingly designed by architects. Naturally ventilated DSFs seem very interesting from an energy point of view, but a good design is crucial to improve the energy savings and the proper operation of the system. Computational Fluid Dynamics (CFD) can play an important role in evaluating and improving the thermal behaviour of a DSF. This paper shows, through a sensitivity analysis, a good strategy for carrying out a CFD simulation of this special building envelope. In this work the validations of the results are based on experimental data from the literature. The paper provides a discussion that highlights which factors are important in the simulation, and which increase model complexity without improving the prediction capacity. The results show that, for a DSF characterized by a prevalent bidirectional flow, the additional effort required to make a 3D model is not justified by a significant improvement of the results. This work shows also that the accuracy can be improved by modelling outdoor ambient. The performance of k-epsilon and k-omega, the two most commonly used turbulent models for simulating the naturally ventilated DSF is evaluated. (C) 2011 Elsevier Ltd. All rights reserved.
引用
收藏
页码:267 / 274
页数:8
相关论文
共 20 条
[1]   Possibilities and limitations of natural ventilation in restored industrial archaeology buildings with a double-skin facade in Mediterranean climates [J].
Ballestini, G ;
De Carli, M ;
Masiero, N ;
Tombola, G .
BUILDING AND ENVIRONMENT, 2005, 40 (07) :983-995
[2]   Experiments on turbulent natural convection in an enclosed tall cavity [J].
Betts, PL ;
Bokhari, IH .
INTERNATIONAL JOURNAL OF HEAT AND FLUID FLOW, 2000, 21 (06) :675-683
[3]  
Chen Q., 1988, ASHRAE Transactions, V94, P196
[4]   A procedure for verification, validation, and reporting of indoor environment CFD analyses [J].
Chen, QY ;
Srebric, J .
HVAC&R RESEARCH, 2002, 8 (02) :201-216
[5]  
Chen QY, 1997, ASHRAE TRAN, V103, P178
[6]  
Chou P.Y., 1945, Q APPL MATH, V1, P33
[7]  
EnergyPlus Development Team, 2010, 6 0 INP OUTP REF ENC
[8]  
FLUENT Inc, 2005, FLUENT 6 3 US GUID
[9]   Greenhouse effect in double-skin facade [J].
Gratia, Elisabeth ;
De Herde, Andre .
ENERGY AND BUILDINGS, 2007, 39 (02) :199-211
[10]  
Kolmogorov A. N., 1942, IZV AN SSSR FIZ, V6, P56