A Control Structure for Smooth Transfer From Grid-Connected to Islanded Operation of Distributed Synchronous Generators

被引:11
作者
Piardi, Artur B. [1 ]
Geraldi Jr, Edson L. [2 ]
Grilo, Ahda P. [3 ]
Reginatto, Romeu [4 ]
Ramos, Rodrigo A. [5 ]
机构
[1] Itaipu Technol Pk Fdn, Lab Automat & Simulat Elect Syst, BR-85867900 Foz Do Iguacu, Brazil
[2] Fed Ctr Technol Educ Minas Gerais, Elect Dept, BR-37250000 Nepomuceno, Brazil
[3] Fed Univ ABC, BR-09210580 Santo Andre, SP, Brazil
[4] Western Parana State Univ, Ctr Engn & Exact Sci, BR-85867900 Foz Do Iguacu, Brazil
[5] Univ Sao Paulo, Sao Carlos Sch Engn, Dept Elect & Comp Engn, BR-13566590 Sao Carlos, Brazil
关键词
Voltage control; Switches; Reactive power; Generators; Transient analysis; Voltage measurement; Distributed Generation; Islanding; Voltage Control; Reactive Power Control; MODE TRANSFER; ANTIWINDUP; INVERTERS; BUMPLESS; RELAYS;
D O I
10.1109/TPWRD.2019.2931174
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The possibility of operating distributed generation (DG) in islanded mode brings several benefits but still faces some problems, especially related to the transition from a grid-connected to an islanded operating condition. When connected to the main grid, DG units operate in PQ mode. During this transition, their controls must be changed to regulate frequency and voltage. The delay for islanding detection, associated with abrupt changes in the control references, may result in large and detrimental transients. This paper proposes a new control structure for a distributed synchronous generator (DSG) to allow a smooth transition from the grid-connected to the islanded operation mode. The proposed control structure uses a compensation loop that was conceived based on the main ideas of the anti-windup bumpless transfer (AWBT) theory (although it is not, strictly speaking, an AWBT controller). The results show that the proposed structure ensures smaller excursions of the DSG variables during the transition and, therefore, the possibility of a successful formation of the islanded system is extended to a wider range of operating conditions. Moreover, with the proposed control, the success of this transition does not depend on the islanding detection time, which is the main contribution of this paper.
引用
收藏
页码:929 / 936
页数:8
相关论文
共 32 条
  • [21] Hierarchical Control System for Robust Microgrid Operation and Seamless Mode Transfer in Active Distribution Systems
    Mohamed, Yasser Abdel-Rady I.
    Radwan, Amr A.
    [J]. IEEE TRANSACTIONS ON SMART GRID, 2011, 2 (02) : 352 - 362
  • [22] Modified centralized ROCOF based load shedding scheme in an islanded distribution network
    Mokari-Bolhasan, Amin
    Seyedi, Heresh
    Mohammadi-ivatloo, Behnam
    Abapour, Saeed
    Ghasemzadeh, Saeed
    [J]. INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2014, 62 : 806 - 815
  • [23] Anti-windup, bumpless, and conditioned transfer techniques for PID controllers
    Peng, YB
    Vrancic, D
    Hanus, R
    [J]. IEEE CONTROL SYSTEMS MAGAZINE, 1996, 16 (04): : 48 - 57
  • [24] Improvement of reliability in active networks with intentional islanding
    Pilo, F
    Celli, G
    Mocci, S
    [J]. PROCEEDINGS OF THE 2004 IEEE INTERNATIONAL CONFERENCE ON ELECTRIC UTILITY DEREGULATION, RESTRUCTURING AND POWER TECHNOLOGIES, VOLS 1 AND 2, 2004, : 474 - 479
  • [25] On electrical power evaluation in dq coordinates under sinusoidal unbalanced conditions
    Reginatto, Romeu
    Ramos, Rodrigo A.
    [J]. IET GENERATION TRANSMISSION & DISTRIBUTION, 2014, 8 (05) : 976 - 982
  • [26] A Practical Method for Nondetection Zone Estimation of Passive Anti-Islanding Schemes Applied to Synchronous Distributed Generators
    Salles, Diogo
    Freitas, Walmir
    Vieira, Jose C. M.
    Venkatesh, Bala
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2015, 30 (05) : 2066 - 2076
  • [27] Trindade F. C. L., 2010, P IEEE PES GEN M, P1, DOI 10.1109/PES.2010.5589547
  • [28] Characteristics of voltage relays for embedded synchronous generators protection
    Vieira, J. C. M.
    Freitas, W.
    Salles, D.
    [J]. IET GENERATION TRANSMISSION & DISTRIBUTION, 2007, 1 (03) : 484 - 491
  • [29] An investigation on the nondetection zones of synchronous distributed generation anti-islanding protection
    Vieira, Jose C. M.
    Freitas, Walmir
    Xu, Wilsun
    Morelato, Andre
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2008, 23 (02) : 593 - 600
  • [30] Seamless Transfer of Single-Phase Grid-Interactive Inverters Between Grid-Connected and Stand-Alone Modes
    Yao, Zhilei
    Xiao, Lan
    Yan, Yangguang
    [J]. IEEE TRANSACTIONS ON POWER ELECTRONICS, 2010, 25 (06) : 1597 - 1603