Hybrid Microgrid Energy Management and Control Based on Metaheuristic-Driven Vector-Decoupled Algorithm Considering Intermittent Renewable Sources and Electric Vehicles Charging Lot

被引:22
作者
Aljohani, Tawfiq M. [1 ]
Ebrahim, Ahmed F. [1 ]
Mohammed, Osama [1 ]
机构
[1] Florida Int Univ, Dept Elect & Comp Engn, Energy Syst Res Lab, Miami, FL 33174 USA
关键词
Energy management and control; particle swarm optimization (PSO); hybrid AC; DC microgrid; electric vehicle charging and discharging control; artificial physics optimization (APO); DESIGN; SYSTEM; OPTIMIZATION; CONVERTER;
D O I
10.3390/en13133423
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Energy management and control of hybrid microgrids is a challenging task due to the varying nature of operation between AC and DC components which leads to voltage and frequency issues. This work utilizes a metaheuristic-based vector-decoupled algorithm to balance the control and operation of hybrid microgrids in the presence of stochastic renewable energy sources and electric vehicles charging structure. The AC and DC parts of the microgrid are coupled via a bidirectional interlinking converter, with the AC side connected to a synchronous generator and portable AC loads, while the DC side is connected to a photovoltaic system and an electric vehicle charging system. To properly ensure safe and efficient exchange of power within allowable voltage and frequency levels, the vector-decoupled control parameters of the bidirectional converter are tuned via hybridization of particle swarm optimization and artificial physics optimization. The proposed control algorithm ensures the stability of both voltage and frequency levels during the severe condition of islanding operation and high pulsed demands conditions as well as the variability of renewable source production. The proposed methodology is verified in a state-of-the-art hardware-in-the-loop testbed. The results show robustness and effectiveness of the proposed algorithm in managing the real and reactive power exchange between the AC and DC parts of the microgrid within safe and acceptable voltage and frequency levels.
引用
收藏
页数:19
相关论文
共 32 条
[1]  
Aljohani T., 2020, P 2020 IEEE INT C EN, P1
[2]  
Aljohani T.M., 2017, SMART GRID RENEW ENE, V8, P240, DOI [10.4236/sgre.2017.87016, DOI 10.4236/SGRE.2017.87016]
[3]  
Aljohani T.M., 2017, Journal of Power and Energy Engineering, V5, P30
[4]   Life Cycle Assessment to Study the Impact of the Regional Grid Mix and Temperature Differences on the GHG Emissions of Battery Electric and Conventional Vehicles [J].
Aljohani, Tawfiq ;
Alzahrani, Ghurmallah .
2019 IEEE SOUTHEASTCON, 2019,
[5]   Single and Multiobjective Optimal Reactive Power Dispatch Based on Hybrid Artificial Physics-Particle Swarm Optimization [J].
Aljohani, Tawfiq M. ;
Ebrahim, Ahmed F. ;
Mohammed, Osama .
ENERGIES, 2019, 12 (12)
[6]  
[Anonymous], P IEEE INT C NEUR NE
[7]   Photovoltaics in Microgrids [J].
Bacha, Seddik ;
Picault, Damien ;
Burger, Bruno ;
Etxeberria-Otadui, Ion ;
Martins, Joao .
IEEE INDUSTRIAL ELECTRONICS MAGAZINE, 2015, 9 (01) :33-46
[8]  
Elsayed A., 2015, SOUTHEASTCON 2015, P1, DOI DOI 10.1109/SECON.2015.7132915
[9]   Optimal choice and design of different topologies of DC-DC converter used in PV systems, at different climatic conditions in Egypt [J].
Farahat, M. A. ;
Metwally, H. M. B. ;
Mohamed, Ahmed Abd-Elfatah .
RENEWABLE ENERGY, 2012, 43 :393-402
[10]  
Ghareeb A.T., 2013, 2013 IEEE Power Energy Society General Meeting, P1