Sub-ambient non-evaporative fluid cooling with the sky

被引:452
作者
Goldstein, Eli A. [1 ]
Raman, Aaswath P. [1 ]
Fan, Shanhui [1 ]
机构
[1] Stanford Univ, Edward L Ginzton Lab, 348 Via Pueblo, Stanford, CA 94305 USA
关键词
SYSTEM; CLIMATE;
D O I
10.1038/nenergy.2017.143
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Cooling systems consume 15% of electricity generated globally and account for 10% of global greenhouse gas emissions. With demand for cooling expected to grow tenfold by 2050, improving the efficiency of cooling systems is a critical part of the twenty-first-century energy challenge. Building upon recent demonstrations of daytime radiative sky cooling, here we demonstrate fluid cooling panels that harness radiative sky cooling to cool fluids below the air temperature with zero evaporative losses, and use almost no electricity. Over three days of testing, we show that the panels cool water up to 5 degrees C below the ambient air temperature at water flow rates of 0.2 l min(-1) m(-2), corresponding to an effective heat rejection flux of up to 70 W m(-2). We further show through modelling that, when integrated on the condenser side of the cooling system of a two-storey office building in a hot dry climate (Las Vegas, USA), electricity consumption for cooling during the summer could be reduced by 21% (14.3 MWh).
引用
收藏
页数:7
相关论文
共 22 条
[1]   A night cold storage system enhanced by radiative cooling - a modified Australian cooling system [J].
Al-Nimr, M ;
Tahat, M ;
Al-Rashdan, M .
APPLIED THERMAL ENGINEERING, 1999, 19 (09) :1013-1026
[2]  
[Anonymous], 2016, 2016 ASHRAE HDB HEAT
[3]  
[Anonymous], 2008, ANN BOT-LONDON, DOI DOI 10.1093/OXFORDJOURNALS.AOB.A088087
[4]   Daytime space cooling with phase change material ceiling panels discharged using rooftop photovoltaic/thermal panels and night-time ventilation [J].
Bourdakis, Eleftherios ;
Pean, Thibault Q. ;
Gennari, Luca ;
Olesen, Bjarne W. .
SCIENCE AND TECHNOLOGY FOR THE BUILT ENVIRONMENT, 2016, 22 (07) :902-910
[5]  
Deru M, 2011, Commercial reference building models of the national building stock
[6]  
Dobson R.T., 2005, Journal of Energy in Southern Africa, V16, P56, DOI [10.17159/2413-3051/2005/V16I2A3184, DOI 10.17159/2413-3051/2005/V16I2A3184]
[7]  
FACIUS T, 2011, TECH REP
[8]  
Fernandez N, 2015, PNNL24904
[9]   A Subambient Open Roof Surface under the Mid-Summer Sun [J].
Gentle, Angus R. ;
Smith, Geoff B. .
ADVANCED SCIENCE, 2015, 2 (09)
[10]   Potential energy savings by radiative cooling system for a building in tropical climate [J].
Hanif, M. ;
Mahlia, T. M. I. ;
Zare, A. ;
Saksandan, T. J. ;
Metselaar, H. S. C. .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2014, 32 :642-650