An Improved Control Method for a DFIG in a Wind Turbine under an Unbalanced Grid Voltage Condition

被引:21
作者
Lee, Sol-Bin [1 ]
Lee, Kyo-Beum [1 ]
Lee, Dong-Choon [2 ]
Kim, Jang-Mok [3 ]
机构
[1] Ajou Univ, Sch Elect & Comp Engn, Suwon 441749, South Korea
[2] Yeungnam Univ, Dept Elect Engn, Gyeongbuk, South Korea
[3] Pusan Natl Univ, Dept Elect Engn, Pusan, South Korea
关键词
Doubly fed induction generator; Unbalanced disturbance; Torque oscillation; DC voltage ripple; Power generation control; Power theory; FED INDUCTION GENERATOR; DIRECT POWER-CONTROL;
D O I
10.5370/JEET.2010.5.4.614
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents a control method, which reduces the pulsating torque and DC voltage problems of a doubly fed induction generator (DFIG)-based wind turbine system. To reduce the torque and power ripple, a current control scheme consisting of a proportional integral (PI) controller is presented in a positive synchronously rotating reference frame, which is capable of providing precise current control for a rotor-side converter with separated positive and negative components. The power theory can reduce the oscillation of the DC-link voltage in the grid-side converter. In this paper, the generator model is examined, and simulation results are obtained with a 3 kW DFIG-based wind turbine system to verify the proposed control strategy.
引用
收藏
页码:614 / 622
页数:9
相关论文
共 17 条
[1]   Control of back-to-back PWM converters for DFIG wind turbine systems under unbalanced grid voltage [J].
Abo-Khalil, Ahmed G. ;
Lee, Dong-Choon ;
Jang, Jeong-Ik .
2007 IEEE INTERNATIONAL SYMPOSIUM ON INDUSTRIAL ELECTRONICS, PROCEEDINGS, VOLS 1-8, 2007, :2637-+
[2]  
ACKERMANN T, 2005, WIND POWER POWER SYS, V1, P58
[3]   Control of a doubly fed induction wind generator under unbalanced grid voltage conditions [J].
Brekken, Ted K. A. ;
Mohan, Ned .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 2007, 22 (01) :129-135
[4]   Dynamic model for doubly-fed induction generators with unbalanced excitation, both with and without winding faults [J].
Djurovic, S. ;
Williamson, S. ;
Renfrew, A. .
IET ELECTRIC POWER APPLICATIONS, 2009, 3 (03) :171-177
[5]   Control of DFIG-based wind generation for power network support [J].
Hughes, FM ;
Anaya-Lara, O ;
Jenkins, N ;
Strbac, G .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2005, 20 (04) :1958-1966
[6]   Performance Improvement of LCL-Filter-Based Grid-Connected Inverters Using PQR Power Transformation [J].
Jeong, Hea-Gwang ;
Lee, Kyo-Beum ;
Choi, Sewan ;
Choi, Woojin .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2010, 25 (05) :1320-1330
[7]  
Jou ST, 2009, J POWER ELECTRON, V9, P781
[8]  
Kim YS, 2009, J POWER ELECTRON, V9, P612
[9]   Reduction of Current Ripples due to Current Measurement Errors in a Doubly Fed Induction Generator [J].
Park, Gwi-Geun ;
Hwang, Seon-Hwan ;
Kim, Jang-Mok ;
Lee, Kyo-Beum ;
Lee, Dong-Choon .
JOURNAL OF POWER ELECTRONICS, 2010, 10 (03) :313-319
[10]  
PATRICK S, 2009, IEEE T IND APPL, V45, P1879