A Single-Ended Fault Location Method for Grid-Connected Converter System Based on Control and Protection Coordination

被引:14
作者
Chang, Peng [1 ]
Song, Guobing [1 ]
Hou, Junjie [1 ]
Xu, Ruidong [1 ]
机构
[1] Xi An Jiao Tong Univ, Sch Elect Engn, Xian 710049, Peoples R China
关键词
Fault location; Mathematical models; Control systems; Resistance; Impedance; Voltage control; Inductance; grid-connected converter system; two-stage control strategy; control and protection coordination; CONTROL STRATEGY; VOLTAGE;
D O I
10.1109/TPWRD.2021.3122976
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Traditional single-ended fault location method is influenced by the fault resistance, and the remote in feed, which reflects as the two equations built by fault phase have four unknowns. And in the grid-connected converter system, the weak feedback characteristic further reduces the performance of the method. To solve it, a single-ended fault location method based on control and protection coordination is proposed in this paper. First, using the high controlled-ability of the converter, the control strategy for fault ride-through (FRT) operation is divided into two stages by switching control modes. Then, according to the electrical quantities under two stages, four uncorrelated equations can be established, and the equations still have four unknown parameters. The fault distance can be calculated by solving them. The simulation results show that the proposed method has high accuracy and is immune to fault resistance and fault location, it solves the problem of insufficient equations in principle.
引用
收藏
页码:3071 / 3081
页数:11
相关论文
共 24 条
[21]  
Teodorescu R, 2011, GRID CONVERTERS FOR PHOTOVOLTAIC AND WIND POWER SYSTEMS, P1, DOI 10.1002/9780470667057
[22]   Improved schemes for traditional current-based phase selectors in wind power systems [J].
Zhang, Jinhua ;
Zhang, Baohui ;
Wang, Chenqing .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2018, 12 (21) :5781-5788
[23]   Improved Continuous Fault Ride Through Control Strategy of DFIG-Based Wind Turbine During Commutation Failure in the LCC-HVDC Transmission System [J].
Zhang, Tian ;
Yao, Jun ;
Sun, Peng ;
Pei, Jinxin ;
Zhang, Hailin ;
Liu, Kai ;
Zhao, Yang .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2021, 36 (01) :459-473
[24]   A Novel Distance Protection Algorithm for the Phase-Ground Fault [J].
Zhong, Ying ;
Kang, Xiaoning ;
Jiao, Zaibin ;
Wang, Zengchao ;
Suonan, Jiale .
IEEE TRANSACTIONS ON POWER DELIVERY, 2014, 29 (04) :1718-1725