Second-law analysis of two-stage vapour compression refrigeration plants

被引:4
作者
Torrella, E. [2 ]
Llopis, R. [1 ]
Cabello, R. [1 ]
Sanchez, D. [1 ]
Larumbe, J. A. [2 ]
机构
[1] Jaume I Univ, Dept Mech Engn & Construct, E-12071 Castellon de La Plana, Spain
[2] Univ Politecn Valencia, Dept Appl Thermodynam, E-46022 Valencia, Spain
关键词
R-404A; exergy analysis; inter-stage pressure; two-stage refrigerating cycle; vapour compression; COMPOUND COMPRESSOR; SYSTEM; CYCLE;
D O I
10.1504/IJEX.2010.035512
中图分类号
O414.1 [热力学];
学科分类号
摘要
This paper describes a Second Law Analysis based on experimental data of a two-stage vapour compression facility driven by a compound compressor for medium and low-capacity refrigeration applications, which operates with the most usual inter-stage configurations (direct liquid injection and subcooler). The experimental analysis is performed for an evaporating temperature range between 36 degrees C and 20 degrees C and for a condensing temperature range between 30 degrees C and 47 degrees C using the refrigerant R-404A. The final results are compared with energy analysis from previous works. Additionally, a new criterion of equivalence between the simple vapour compression cycle and the two-stage compression cycle is given.
引用
收藏
页码:641 / 653
页数:13
相关论文
共 15 条
[1]  
[Anonymous], HVAC RES
[2]  
[Anonymous], INT J EXERGY
[3]   Theoretical analysis of a vapour compression refrigeration system with R502, R404A and R507A [J].
Arora, Akhilesh ;
Kaushik, S. C. .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2008, 31 (06) :998-1005
[4]  
*ASHRAE, 2005, 2005 HDB FUND
[5]   Fundamentals of exergy analysis, entropy generation minimization, and the generation of flow architecture [J].
Bejan, A .
INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2002, 26 (07) :545-565
[6]   Design and rating of a two-stage vapor-compression refrigeration system [J].
Khan, JUR ;
Zubair, SM .
ENERGY, 1998, 23 (10) :867-878
[7]   Exergy-method analysis of a two-stage vapour-compression refrigeration-plants performance [J].
Nikolaidis, C ;
Probert, D .
APPLIED ENERGY, 1998, 60 (04) :241-256
[8]   Second law analysis of two-stage compression transcritical CO2 heat pump cycle [J].
Oezguer, Arif Emre ;
Bayrakci, Hilmi Cenk .
INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2008, 32 (13) :1202-1209
[9]  
RANT Z, 1963, GASWARME, V12, P297
[10]  
RANT Z, 1963, GASWARME INT, V12, P304