Energy, exergy and exergoeconomic evaluation of the air source transcritical CO2 heat pump with internal heat exchanger for space heating

被引:37
作者
Wang, Yikai [1 ]
Ye, Zuliang [1 ]
Yin, Xiang [1 ]
Song, Yulong [1 ]
Cao, Feng [1 ]
机构
[1] Xi An Jiao Tong Univ, Sch Energy & Power Engn, 28 Xianning West Rd, Xian 710049, Peoples R China
基金
中国国家自然科学基金;
关键词
transcritical CO2 heat pump; Internal heat exchanger; Energy analysis; Exergy analysis; Exergoeconomic analysis; Sensitivity analysis; PERFORMANCE; SYSTEM; OPTIMIZATION; EXPANDER; EJECTOR;
D O I
10.1016/j.ijrefrig.2021.06.028
中图分类号
O414.1 [热力学];
学科分类号
摘要
Currently, the air source heat pump is widely used for space heating. Although the CO2 has great potential in the refrigeration system, the basic transcritical CO2 heat pump performance is restricted by the huge throttling irreversibility caused by the higher gas cooler outlet temperature. The internal heat exchanger has been investigated extensively from the energetic perspective. However, little information is available about the exergy analysis, let alone the exergoeconomic analysis. In this paper, the transcritical CO2 heat pump with/without the internal heat exchanger is studied with the energy, exergy, and exergoeconomic analysis. Results show that the optimal coefficient of performance can be increased to 2.96 and 2.17 in the different heating terminals. The enlarged internal heat exchanger effectiveness is also beneficial to reduce the optimal discharge pressure and increased the system coefficient of performance. The throttling valve irreversibility is decreased from 0.067 to 0.145 kW.kW(-1) to 0.040-0.071 kW.kW(-1). With total irreversibility decrement, the exergy efficiency can be effectively improved, resulting in the 55.65%-73.42% reduction of the throttle valve cost rate. Considering the CO2 compressor investment, its total exergy cost rate increment is reached up to 34.06%-50.21%, leading to the higher exergoeconomic factor. However, the sensitivity analysis results show that the cost per unit of exergy production is more sensitive to the electricity price. Moreover, the optimal cost per unit of exergy production reduction is declined by 58.71% with the return water temperature of 30 degrees C.
引用
收藏
页码:14 / 26
页数:13
相关论文
共 35 条
[1]  
[Anonymous], 2014, Off. J. Eur. Union, VL150, P195
[2]   Comparative assessment of solar and heat pump dryers with regards to exergy and exergoeconomic performance [J].
Atalay, Halil .
ENERGY, 2019, 189
[3]   Optimization study of heat pumps using refrigerant blends - Ejector versus expansion valve systems [J].
Brodal, Eivind ;
Eiksund, Oddmar .
INTERNATIONAL JOURNAL OF REFRIGERATION, 2020, 111 :136-146
[4]   Experimental investigation on the influence of internal heat exchanger in a transcritical CO2 heat pump water heater [J].
Cao, Feng ;
Ye, Zuliang ;
Wang, Yikai .
APPLIED THERMAL ENGINEERING, 2020, 168
[5]   Theoretical analysis of internal heat exchanger in transcritical CO2 heat pump systems and its experimental verification [J].
Cao, Feng ;
Wang, Yikai ;
Ye, Zuliang .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2019, 106 :506-516
[6]  
Dai B.M., ENERGY CONVERS MANAG, V210
[7]  
Dai B.M., ENERGY CONVERS MANAG, V209
[8]   Environmental and economical analyses of transcritical CO2 heat pump combined with direct dedicated mechanical subcooling (DMS) for space heating in China [J].
Dai, Baomin ;
Qi, Haifeng ;
Liu, Shengchun ;
Zhong, Zhifeng ;
Li, Hailong ;
Song, Mengjie ;
Ma, Muyu ;
Sun, Zhili .
ENERGY CONVERSION AND MANAGEMENT, 2019, 198
[9]   Evaluation of transcritical CO2 heat pump system integrated with mechanical subcooling by utilizing energy, exergy and economic methodologies for residential heating [J].
Dai, Baomin ;
Qi, Haifeng ;
Liu, Shengchun ;
Ma, Muyu ;
Zhong, Zhifeng ;
Li, Hailong ;
Song, Mengjie ;
Sun, Zhili .
ENERGY CONVERSION AND MANAGEMENT, 2019, 192 :202-220
[10]   Experimental performance analysis of a CO2 direct-expansion solar assisted heat pump water heater [J].
Duarte, Willian M. ;
Rabelo, Sabrina N. ;
Paulino, Tiago F. ;
Pabon, Juan J. G. ;
Machado, Luiz .
INTERNATIONAL JOURNAL OF REFRIGERATION, 2021, 125 :52-63