Saturated flow boiling heat transfer and pressure drop of refrigerant R-410A in a vertical plate heat exchanger

被引:207
作者
Hsieh, YY [1 ]
Lin, TF [1 ]
机构
[1] Natl Chiao Tung Univ, Dept Mech Engn, Hsinchu 30010, Taiwan
关键词
D O I
10.1016/S0017-9310(01)00219-8
中图分类号
O414.1 [热力学];
学科分类号
摘要
Saturated flow boiling heat transfer and the associated frictional pressure drop of the ozone friendly refrigerant R-410A (a mixture of 50 wt% R-32 and 50 wt% R-125) flowing in a vertical plate heat exchanger (PHE) are investigated experimentally in the study. In the experiment two vertical counter flow channels are formed in the exchanger by three plates of commercial geometry with a corrugated sinusoidal shape of a chevron angle of 60degrees. Upflow boiling of saturated refrigerant R-410A in one channel receives heat from the downflow of hot water in the other channel. The experimental parameters in this study include the refrigerant R-410A mass flux ranging from 50 to 125 kg/m(2) s and imposed heat flux from 5 to 35 kW/m(2) for the system pressure fixed at 1.08, 1.25 and 1.44 MPa, which respectively correspond to the saturated temperatures of 10, 15 and 20degreesC. The measured data showed that both the boiling heat transfer coefficient and frictional pressure drop increase almost linearly with the imposed heat flux. Furthermore, the refrigerant mass flux exhibits significant effect on the saturated flow boiling heat transfer coefficient only at higher imposed heat flux. For a rise of the refrigerant pressure from 1.08 to 1.44 MPa, the frictional pressure drops are found to be lower to a noticeable degree. However, the refrigerant pressure has very slight influences on the saturated flow boiling heat transfer coefficient. Finally, empirical correlations are proposed to correlate the present data for the saturated boiling heat transfer coefficients and friction factor in terms of the Boiling number and equivalent Reynolds number. (C) 2002 Elsevier Science Ltd. All rights reserved.
引用
收藏
页码:1033 / 1044
页数:12
相关论文
共 26 条
[1]   Working fluids for mechanical refrigeration - Invited paper presented at the 19th International Congress of Refrigeration, The Hague, August 1995 [J].
Cavallini, A .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1996, 19 (08) :485-496
[2]  
CHIANG LJ, 2000, THESIS NATL CHAIO TU
[3]   Evaporation heat transfer for R-22 and R-407C refrigerant-oil mixture in a microfin tube with a U-bend [J].
Cho, K ;
Tae, SJ .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2000, 23 (03) :219-231
[4]   Evaporation heat transfer of R-32, R-134a, R-32/134a, and R-32/125/134a inside a horizontal smooth tube [J].
Choi, TY ;
Kim, YJ ;
Kim, MS ;
Ro, ST .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2000, 43 (19) :3651-3660
[5]  
Collier J.G., 1982, Convective Boiling and Condensation, V2nd
[6]  
Ebisu T., 1998, ASHRAE T, V19, P556
[7]   Heat transfer and pressure drop during condensation of refrigerant 134a in an axially grooved tube [J].
Graham, D ;
Chato, JC ;
Newell, TA .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 1999, 42 (11) :1935-1944
[8]   Condensation of R134a flowing inside helicoidal pipe [J].
Kang, HJ ;
Lin, CX ;
Ebadian, MA .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2000, 43 (14) :2553-2564
[9]  
Kline S.J., 1952, ASME Mechanical Engineering, V75, P3, DOI DOI 10.1016/J.CHAOS.2005.11.046
[10]   Experimental study of turbulent flow heat transfer and pressure drop in a plate heat exchanger with chevron plates [J].
Muley, A ;
Manglik, RM .
JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 1999, 121 (01) :110-117